Digital Input / Output Descriptor; Dio Sensor Type; Dio Data Type/Format; Data Type - Omega SP-014 User Manual

Process monitoring smart probe
Hide thumbs Also See for SP-014:
Table of Contents

Advertisement

5.2

Digital Input / Output Descriptor

The DIO Interface provides 2 digital inputs which are hardwired to the digital outputs. These may be used to detect the
state of external switches (output off) or to monitor the state of the outputs. The DIO Input descriptor is at base addresses
0x0068.
0x04..0x08

5.2.1 DIO Sensor Type

The interface provides a bit mapped input of the 2 digital signal lines.

5.2.2 DIO Data Type/Format

7

Smart Sensor

0
Note:
Please refer to the Smart Sensor Interface Technical Guide for more information regarding this descriptor.

5.2.2.1 Data Type

The 4-bit Data Type field determines the type of date of the specific sensor.

5.2.2.2 Factory Calibrate

The Factory Calibrate bit is not used for DIO types.

5.2.2.3 Sensor Writeable

If the Sensor Writeable bit is set the sensor value may be overwritten with a preset value.
5.2.2.4 Smart Sensor
Refer to the Smart Sensor Device Interface documentation.

5.2.3 DIO Input Configuration

7
Available
0

5.2.3.1 Lock

If set, the user specified units of measure string (4-character maximum) will be used in place of the default DIN.
Offset
Name
0x00
Sensor Type
0x01
Data Type/Format
0x02
Configuration
0x03
Sensor Device
UOMR
Sensor Type
SI Derived Units
0x18
6
5
Sensor
Factory
Writable
Calibrate
0
0
6
5
Assigned
Apply
Scaling
0
1
Value
0x18
Digital Type (Bit mapped)
0x46
Configurable, Float type
0x23
Scaling applied, Bits 0 and 1 enabled
0x0f
DIN bits enabled / inverted
"DIN"
Units of measure
Measurement
DIN
Bit mapped digital inputs
DIO Data Type
4
3
reserved
0
DIO Input Configuration
4
3
Lock
?
Description
2
1
Data Type
6 == Floating point
2
1
Sub Channel Selection
0x03 == bits 0 and 1
0
0
14 |
P a g e

Advertisement

Table of Contents
loading

Table of Contents