Symbols used Document ID This symbol on the front page of this instruction refers to the Docu- ment ID. By entering the Document ID on www.vega.com you will reach the document download. Information, note, tip: This symbol indicates helpful additional infor- mation and tips for successful work.
During work on and with the device, the required personal protective equipment must always be worn. Appropriate use The VEGAPOINT 24 is a sensor for point level detection. You can find detailed information about the area of application in chapter " Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
Safety instructions for Ex areas For applications in explosion-proof areas (Ex), only devices with cor- responding Ex approval may be used. Observe the Ex-specific safety instructions. These are an integral part of the operating instructions and are enclosed with every device with Ex approval. VEGAPOINT 24 • Transistor with IO-Link...
This operating instructions manual applies to the following instrument instructions versions: • Hardware version from 1.0.0 • Software version from 1.0.0 Constituent parts The VEGAPOINT 24 consists of the components: • Housing with integrated electronics • Process fitting • Plug (optional) Fig. 1: VEGAPOINT 24 360°...
Principle of operation Application area The VEGAPOINT 24 is a combined capacitive and conductive point level sensor for point level detection. It is designed for industrial applications and is particularly suitable for point level detection in heavily adhering and/or pasty media or if a front-flush installation is required.
3 Product description The mechanical structure prevents abrasion effects. Typical applications are overfill and dry run protection. With a the small sensor unit, VEGAPOINT 24 can be also mounted e.g. in thin pipelines. The sensor allows use in vessels, tanks and pipes. Thanks to its simple and robust measuring system, VEGAPOINT 24 is virtual- ly unaffected by the chemical and physical properties of the medium.
Unless otherwise indicated, the packages must be stored only under the following conditions: • Not in the open • Dry and dust free • Not exposed to corrosive media • Protected against solar radiation • Avoiding mechanical shock and vibration VEGAPOINT 24 • Transistor with IO-Link...
The instructions for the listed accessories can be found in the down- load area on our homepage. Threaded and hygienic Various threaded and hygienic sockets are available for devices with socket threaded version. You can find further information in the "Technical data" VEGAPOINT 24 • Transistor with IO-Link...
Chemical properties of the medium • Abrasion and mechanical influences Switching point The VEGAPOINT 24 can be mounted in any position. The instrument must be mounted in such a way that the sensor is at the height of the requested switching point. Fig. 4: Installation examples 1 Upper level detection (max.) as overflow protection...
In the upper part of the pipe cavities can form due to air inclusions. Solids can settle in the lower pipe area. Both can lead to measure- ment errors. In horizontal pipelines, lateral installation is therefore recommended. VEGAPOINT 24 • Transistor with IO-Link...
Page 14
GAPOINT 24 at a position in the vessel where no disturbances, e.g. from filling openings, agitators, etc., can occur. Food applications In food or pharmaceutical application in which an agitator scrapes the filling product from the vessel wall, you should install the sensor set back by 2 mm (0.08 in). This protects the plastic scrapers of the agitator from being damaged. VEGAPOINT 24 • Transistor with IO-Link...
Page 15
4 Mounting Fig. 7: VEGAPOINT 24 2 mm (0.08 in) set back in food application VEGAPOINT 24 • Transistor with IO-Link...
EN 61326-1 for industrial areas, shielded cable should be used. Connecting Instrument versions Fig. 8: Instrument versions Device version with housing 316L and plastic Device version with full metal housing 316L 360° status indication VEGAPOINT 24 • Transistor with IO-Link...
Contact, plug connector Function/Polarity Voltage supply/+ Transistor output 2 Voltage supply/- Transistor output 1/IO-Link Switch-on phase After switching on, the device first carries out a self-test in which the function of the electronics is checked. The current measured value is then output on the signal cable. VEGAPOINT 24 • Transistor with IO-Link...
If this document is lost, the emergency device code can be retrieved from your personal contact person after legitimation. The storage and transmission of the device codes is always encrypt- ed (SHA 256 algorithm). VEGAPOINT 24 • Transistor with IO-Link...
" PINs and Codes". This greatly simplifies the use of additional adjust- ment tools, as all Bluetooth access and device codes are automati- cally synchronized when connected to the " myVEGA" account VEGAPOINT 24 • Transistor with IO-Link...
There are several ways to operate the device. The Bluetooth version (optional) of the instrument enables a wireless connection to standard adjustment units. This can be smartphones/ Default setting Switching status of output 1 VEGAPOINT 24 • Transistor with IO-Link...
Page 21
Acc. to NAMUR NE 107 Fault Switching output Yellow Operating status Green Access protection Bluetooth access code See supplementary sheet "PINs and Codes". Protection of the parameterization Deactivated Reset Units Temperature unit °C Only for "User-defined" application VEGAPOINT 24 • Transistor with IO-Link...
If you have selected the application User-defined you can adjust the switching states with the original medium or with the actual covering state. Depending on the selected application, you can produce the cor- responding occultation states and transfer them directly. Only DTM adjustment VEGAPOINT 24 • Transistor with IO-Link...
Page 23
You can enter the determined values for both outputs " Together" or " Separate ". If you select the adjustment " Separate", you can set a different switching threshold for the second output. Adjust outputs - Together • Uncovered • Covered VEGAPOINT 24 • Transistor with IO-Link...
Page 24
Only when the reset point (RP) is reached does the output switch back. If the measured variable moves between switching and reset point, the state of the output does not change. VEGAPOINT 24 • Transistor with IO-Link...
Page 25
In case of a possible repeat order of an identical device, this value can be preconfigured during the customer-specific parameterization. Reset point (RP1) The reset point (RP) controls the sensitivity of the sensor when the sensor tip is released. The value cannot be changed. VEGAPOINT 24 • Transistor with IO-Link...
Page 26
See also chapter " Access protection". Protection of the parameterization In this menu item you can also protect the parameter adjustment of the sensor. For this function you need the six-digit device code. VEGAPOINT 24 • Transistor with IO-Link...
Page 27
In addition, the current value is displayed. • Peak value coverage • Pointer function degree of coverages output 2 • Peak values, electronic temperature In this window you can also reset each of the three pointers individu- ally. VEGAPOINT 24 • Transistor with IO-Link...
Page 28
In this menu item you can simulate the function of the two switching outputs separately. Note: Make sure the connected downstream devices are activated during the simulation. First select the desired switching output and start the simulation. Then select the desired switching state. • Open VEGAPOINT 24 • Transistor with IO-Link...
Page 29
In this menu item you can retrieve the sensor features of the device. This menu item can only be selected via PACTware with DTM. • Order texts • Instrument version • Electronics • etc. VEGAPOINT 24 • Transistor with IO-Link...
• Operating system: Android 5.1 or newer • Bluetooth 4.0 LE or newer Download the VEGA Tools app from the " Apple App Store", " Goog- le Play Store" or " Baidu Store" to your smartphone or tablet. Connecting Connecting Start the adjustment app and select the function "...
The sensor adjustment menu is divided into two halves: On the left you'll find the navigation section with the menus " Setup", " Diagnosis" and others. The selected menu item, recognisable by the colour change, is dis- played in the right half. Fig. 12: Example of an app view - Setup VEGAPOINT 24 • Transistor with IO-Link...
Enter Bluetooth access For authentication, enter in the next menu window the 6-digit code Bluetooth access code: Fig. 13: Enter Bluetooth access code VEGAPOINT 24 • Transistor with IO-Link...
The sensor adjustment menu is divided into two halves: On the left you'll find the navigation section with the menus " Setup", " Display", " Diagnosis" and others. The selected menu item, recognisable by the colour change, is dis- played in the right half. Fig. 14: Example of a DTM view - Setup VEGAPOINT 24 • Transistor with IO-Link...
24 hour service hotline Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550. The hotline is also available outside normal working hours, seven days a week around the clock.
Function check - orange Maintenance required - blue Failure: Due to a malfunction in the instrument, a fault message is output. This status message is always active. It cannot be deactivated by the user. VEGAPOINT 24 • Transistor with IO-Link...
Page 36
Finish simulation Simulation active Wait for the automatic end after 60 mins. Out of specification Code Cause Rectification Text message S600 Temperature of the electronics in the Check ambient temperature non-specified range Impermissible electronics Insulate electronics temperature VEGAPOINT 24 • Transistor with IO-Link...
Clean the instrument and pack it damage-proof • Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Ask the agency serving you to get the address for the return ship- ment. You can find the agency on our homepage. VEGAPOINT 24 • Transistor with IO-Link...
11.2 Disposal The device is made of recyclable materials. For this reason, it should be disposed of by a specialist recycling company. Observe the ap- plicable national regulations. VEGAPOINT 24 • Transistor with IO-Link...
That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observ- ing the environmental instructions in chapters " Packaging, transport and storage", " Disposal" of these operating instructions. VEGAPOINT 24 • Transistor with IO-Link...
50 Nm (37 lbf ft) with O-ring Ʋ With hygiene adapter 1" (AM) 100 Nm (73 lbf ft) metallically sealing Surface quality < 0.76 µm (3.00 Measurement accuracy Hysteresis approx. 1 mm (0.04 in) not in contact with the medium VEGAPOINT 24 • Transistor with IO-Link...
Page 41
App (Android/OS), PACTware with DTM, I/O-Link via DTM, IODD or I/O-Link master Output variable - Transistor output/IO-Link Output signal Transistor output NPN/PNP Output signal IO-Link acc. to IEC 61131-9 Connection technology Three-wire Load current max. 250 mA Overload resistance VEGAPOINT 24 • Transistor with IO-Link...
Page 42
M12 x 1 plug IP66/IP68 (0.2 bar)/IP69 NEMA 6P Altitude above sea level up to 5000 m (16404 ft) Protection class Depending on the local conditions; with M12 x 1 plug stainless steel (closed full metal housing) effective range up to approx. 5 m (16.40 ft) Depending on the instrument version VEGAPOINT 24 • Transistor with IO-Link...
Degree of coverage Out2 Degree of coverage Out1 Out2 Out1 Formats Value Type Out1 1 Bit Boolean Out2 1 Bit Boolean Degree of coverage Out2 14 Bit Integer Degree of coverage Out1 16 Bit Integer VEGAPOINT 24 • Transistor with IO-Link...
Page 44
Software Re- 0x0017 String vision Application 0x0018 Max. 31 String Sensor Specific Tag FunctionTag 0x0019 Max. 31 String LocationTag 0x001A Max. 31 String Device Status 36 0x0024 unsigned8[2] Detailed De- 0x0025 unsigned8[12] RO vice Status VEGAPOINT 24 • Transistor with IO-Link...
Page 45
0 = HNO, 1=HNC 2 = FNO, 3=FNC Brightness illuminated ring 0x0115 Unsigned8 0 … 100% (LED) in 10 % steps Signalling 0x0116 Unsigned8 0 = Individual sig- nalling 1 = acc. to NA- MUR NE 107 VEGAPOINT 24 • Transistor with IO-Link...
Page 46
Individual Signal- ling - switching output Temperature unit (TMP) 0x0123 Float 1001 = °C 1002 = °F Bluetooth access code 0x0124 String (BT) Protection of parameter 0x0125 Unsigned8 0 = deactivated adjustment 1= activated VEGAPOINT 24 • Transistor with IO-Link...
Page 47
1 = Closed Output 2 0x0135 Unsigned16 RO 0 = Open 1 = Closed Device name 0x0136 String Serial number 0x0137 String Hardware version 0x0138 String Software version 0x0139 String Device revision 0x013A Unsigned16 RO VEGAPOINT 24 • Transistor with IO-Link...
Page 48
ISDU (hex) Access Factory Reset 0x082 Reset Pointer - Resonance Frequency 0x0A1 Reset Pointer - Measuring Cell Temperature 0x0A3 Reset Pointer - Electronic Temperature 0x0A4 Uncovered 0x0A5 Covered 0x0A6 Accepting and activating taught-in settings 0x0AC VEGAPOINT 24 • Transistor with IO-Link...
ø 18 mm (0.71") Fig. 16: VEGAPOINT 24, standard version - thread with M12 x 1 plug Thread G½, G¾, G1 (DIN ISO 228/1) with M12 x 1 plug connection (Housing: 316L and plastic) VEGAPOINT 24, hygienic version - Thread...
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.
Page 51
Notes VEGAPOINT 24 • Transistor with IO-Link...