Error Indication - Gree GMV-60WL/C-T Owner's Manual

Dc inverter multi vrf system
Hide thumbs Also See for GMV-60WL/C-T:
Table of Contents

Advertisement

7 Error Indication

Inquiry method of error indication: combine division symbol and content symbol to check the
corresponding error.
Indoor:
Error
Code
L0
Malfunction of IDU (uniform)
L1
Protection of indoor fan
L2
Auxiliary heating protection
L3
Water-full protection
L4
Abnormal power supply for wired controller
L5
Freeze prevention protection
L6
Mode shock
L7
No main IDU
L8
Power supply is insufficient
For single control over multiple units, number of
L9
IDU is inconsistent
For single control over multiple units, IDU series is
LA
inconsistent
LH
Alarm due to bad air quality
LC
IDU is not matching with outdoor unit
LL
Malfunction of water flow switch
LE
Rotation speed of EC DC water pump is abnormal
LF
Malfunction of shunt valve setting
LJ
Setting of functional DIP switch code is wrong
LP
Zero-crossing malfunction of PG motor
Indoor unit's branch is not inconsistent for
LU
one-to-more unit of heat recovery system
Inconsistent IDU of group-controlled reheat and
Lb
dehumidification system
y1
Malfunction of inlet tube temperature sensor 2
y2
Malfunction of outlet tube temperature sensor 2
y7
Malfunction of fresh air intake temperature sensor
yA
IFD malfunction
Outdoor:
Error
Code
F0
Main board of ODU is poor
F1
Malfunction of high-pressure sensor
F3
Malfunction of low-pressure sensor
Malfunction of discharge temperature sensor of
F5
compressor 1
F6
Malfunction of exit-tube temperature sensor
F7
Malfunction of humidity sensor
F8
Malfunction of water temperature sensor
F9
Malfunction of jumper cap
FA
Web address of IDU is abnormal
FC
Current sensor of compressor 2 is abnormal
FL
Current sensor of compressor 3 is abnormal
FE
Current sensor of compressor 4 is abnormal
FF
Current sensor of compressor 5 is abnormal
FJ
Current sensor of compressor 6 is abnormal
Content
Content
Error
Code
d1
Indoor PCB is poor
Malfunction of lower water temperature sensor
d2
of water tank
d3
Malfunction of ambient temperature sensor
d4
Malfunction of entry-tube temperature sensor
d5
Malfunction of middle temperature sensor
d6
Malfunction of exit-tube temperature sensor
d7
Malfunction of humidity sensor
d8
Malfunction of water temperature sensor
d9
Malfunction of jumper cap
dA
Web address of IDU is abnormal
dH
PCB of wired controller is abnormal
dC
Abnormal setting for capacity button
dL
Malfunction of air outlet temperature sensor
dE
Malfunction of indoor CO
Malfunction of upper water temperature sensor
dF
of water tank
dJ
Malfunction of backwater temperature sensor
Malfunction of inlet tube temperature sensor of
dP
generator
Malfunction of drainage pipe temperature sensor
dU
of generator
db
Debugging status
dd
Malfunction of solar power temperature sensor
dn
Malfunction of swing parts
dy
Malfunction of water temperature sensor
y8
Main error of indoor air box sensor
Error
Code
E0
Malfunction of ODU (uniform)
E1
High-pressure protection
E2
Discharge low-temperature protection
E3
Low-pressure protection
High discharge temperature protection of
E4
compressor
Ed
Drive module low temperature protection
J0
Protection for other modules
J1
Over-current protection of compressor 1
J2
Over-current protection of compressor 2
J3
Over-current protection of compressor 3
J4
Over-current protection of compressor 4
J5
Over-current protection of compressor 5
J6
Over-current protection for compressor 6
J7
Gas-mixing protection of 4-way valve
28
DC Inverter Multi VRF System
Content
sensor
2
Content

Advertisement

Table of Contents
loading

Table of Contents