DC Inverter Multi VRF System
5.2.3 Appendix: Reference of Normal Operation Parameters
No.
Debug item
1
2
3
4
System
parameters
parameters
5
6
7
8
9
10
Parameter name
Outdoor
temperature
Compressor
discharge temp
Defrosting temp
System high
pressure
ODU
System low
pressure
Opening degree of
thermal EXV
Compressor's
operating freq
Compressor's
operating current
Compressor's IPM
temp
Fan motor's
operating freq
Unit
°C(°F)
 When compressor starts, discharge temp in
cool mode is within 70~105°C(158~221°F)
and at least 10°C(50°F) higher than the high
pressure saturation temp.
°C(°F)
 As for temp in heat mode, it is within
65~90°C(149~194°F) and at least
10°C(50°F) higher than the high pressure
saturation temp.
 In cool mode, defrosting temp is
4~10°C(39~50°F) lower than system's high
pressure value.
°C(°F)
 In heat mode, defrosting temp is about
2°C(36°F) different from system's low
pressure value.
 In cool mode, the normal high pressure
value is within 20~55°C(68~131°F).
According to the change of ambient temp
and system's operating capacity, the high
pressure value will be 10~30°C(50~86°F)
higher than ambient temp. The higher
ambient temp is, the smaller temp difference
°C(°F)
is. If ambient temp is 25~35°C(77~95°F) in
cool mode, system's high pressure value will
be within 44~53°C(111~127°F).
 In heat mode, if ambient temp is above
-5°C(23°F), system's high pressure value is
within 40~52°C(104~126°F). If ambient temp
is low and many IDUs are turned on, the high
pressure will be lower.
 When ambient temp in cool mode is
25~35°C(77~95°F), the low pressure value
is 0~8°C(32~46°F).
°C(°F)
 When ambient temp in heat mode is above
-5°C(23°F), the low pressure value is
-15~8°C(5~46°F).
 In cool mode, the thermal electronic
expansion valve remains 480PLS.
PLS
 In heat mode, the adjustable opening degree
of EXV is 60~480PLS.
GMV-36WL/C-T(U)
GMV-48WL/C-T(U)
Hz
GMV-60WL/C-T(U)
When compressor works normally, the current
A
is no more than 22.6A.
When ambient temp is below 35°C(95°F), IPM
°C(°F)
temp is lower than 80°C(176°F) and the highest
temp won't be above 95°C(203°F).
GMV-36WL/C-T(U)
GMV-48WL/C-T(U)
Hz
GMV-60WL/C-T(U)
25
Reference
Changes in 10Hz~80Hz.
Changes in 16Hz~80Hz
Changes in 0~49Hz
according to system's
pressure.
Changes in 0~40Hz
according to system's
pressure.