Gree GMV-60WL/C-T Owner's Manual page 10

Dc inverter multi vrf system
Hide thumbs Also See for GMV-60WL/C-T:
Table of Contents

Advertisement

DC Inverter Multi VRF System
4.2.2 Allowable Length and Height Difference of Connection Pipe
Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is shown
in Fig.4.3 below.
Equivalent length of one Y-type branch is 0.5m(1-5/8feet).
Fig.4.3 Allowable Length and Height Difference of Connection Pipe
Piping parameters of GMV-36WL/C-T(U), GMV-48WL/C-T(U), GMV-60WL/C-T(U):
Total length (actual length) of fitting pipe
Length of farthest fitting pipe
From the 1st branch to the farthest indoor pipe
Height difference between ODU
and IDU
Height difference between IDUs
Actual length
Equivalent length
ODU at upper side
ODU at lower side
40
Allowable value
m
feet
300
984
120
394
150
492
40
131
50
164
40
131
15
49
7
Fitting pipe
L1+L2+L3+a+b+c+d
L1+L2+L3+d
L2+L3+d