Gree GMV-60WL/C-T Owner's Manual page 33

Dc inverter multi vrf system
Hide thumbs Also See for GMV-60WL/C-T:
Table of Contents

Advertisement

Error
Code
HE
Phase-lacking of inverter fan
HF
Drive charging circuit malfunction of fan
HJ
Failure startup of inverter fan
HP
AC current protection of inverter fan
HU
AC input voltage of drive of inverter fan
Gd
Grid side current sensor protection
Gn
Insulation resistance protection
Gy
Unrecoverable error of grid drive (photovoltaic)
Debugging:
Error
Code
U0
Preheat time of compressor is insufficient
U2
Wrong setting of ODU's capacity code/jumper cap
U3
Power supply phase sequence protection
U4
Refrigerant-lacking protection
U5
Wrong address for driving board of compressor
U6
Alarm because valve is abnormal
U7
Power grid DRED0 response protection
U8
Short-circuit malfunction of IDU
U9
Malfunction of pipe-line for ODU
UA
DC bus overvoltage protection at power grid side
UH
DC bus undervoltage protection at power grid side
UC
Setting of main IDU is successful
Emergency operation DIP switch code of
UL
compressor is wrong
UE
Charging of refrigerant is invalid
Identification malfunction of IDU of mode
UF
exchanger
UJ
FO protection for PV module
Ud
Grid-connected driver board error
Communication malfunction between main control
Un
and inverter
Uy
Over-temperature protection for PV module
Communication malfunction between IDU and the
CU
receiving lamp plate
Cb
Overflow distribution of IP address
Content
Content
Error
Code
Photovoltaic DC hardware overcurrent
GC
protection
GL
Grid side hardware overcurrent protection
GE
High or low photovoltaic voltage protection
DC bus neutral-point potential unbalance
GF
protection
GJ
Grid side module high-temperature protection
GP
Grid side temperature sensor protection
GU
Charging circuit protection
Gb
Grid side relay protection
Error
Code
Communication malfunction between mode
Cd
exchanger and ODU
Malfunction of network for IDU and ODU of
Cn
mode exchanger
Cy
Communication malfunction of mode exchanger
Communication malfunction between IDU,
C0
ODU and IDU's wired controller
Communication malfunction between main
C1
control and DC-DC controller
Communication malfunction between main
C2
control and inverter compressor driver
Communication malfunction between main
C3
control and inverter fan driver
C4
Malfunction of lack of IDU
Alarm because project code of IDU is
C5
inconsistent
C6
Alarm because ODU quantity is inconsistent
C7
Abnormal communication of converter
C8
Emergency status of compressor
C9
Emergency status of fan
CA
Emergency status of module
CH
Rated capacity is too high
CC
Malfunction of lack of main control unit
CL
Rated capacity is too low
Communication malfunction between mode
CE
exchanger and IDU
CF
Malfunction of multiple main control units
CJ
Address DIP switch code of system is shocking
CP
Malfunction of multiple main wired controllers
30
DC Inverter Multi VRF System
Content
Content