Installation and
operating instructions
File No: 40.85iec
Date: march 05, 2020
Supersedes: 40.85l
Date: december. 10, 2009

Advertisement

Table of Contents
loading

Summary of Contents for Armstrong 4030 Series

  • Page 1 Series 4030 Base mounted pump Installation and operating instructions File No: 40.85iec Date: march 05, 2020 Supersedes: 40.85l Date: december. 10, 2009...
  • Page 3: Table Of Contents

    contents introduction instructions for safe use temperature noise levels storage uncrating handling limitations installation location installation foundation levelling alignment grouting piping final alignment pump piping - general operation starting pump general care lubrication system cleanliness warranty...
  • Page 4: Introduction

    If clarification is term storage, the pump must be placed in a vertical position needed on any point please contact Armstrong quoting the in a dry environment. Internal rusting can be prevented by equipment serial number.
  • Page 5: Limitations

    These limits must insert the anchors. not, under any circumstances be exceeded without prior consultation with Armstrong. Take the tamping tool (supplied with the anchors) and drive home the lead sleeve until it is below the level of the foundation and firmly fixed in important: the concrete.
  • Page 6: Grouting

    49°c ( 120°f ). Use short direct suction piping one or two times larger than Armstrong suction guides may be used in place of the the pump suction nozzle. Arrange piping to eliminate poten- straight pipe run and in-line strainer.
  • Page 7: General Care

    • Do not run the pump against a closed discharge valve for recommended. (See Armstrong files 43 . 85 & 43 . 86 for an extended period of time. (A few minutes maximum) seal environmental instructions).
  • Page 8: System Cleanliness

    Does not cover any damages to the equipment resulting from caution failure to observe the above precautions. Refer to Armstrong The permissible tds levels are : General Terms and Warranty sheet. Contact your local a SSiC Vs C – 2000ppm max Armstrong representative for full information.
  • Page 9 Series 4030 in sta l l a t io n & Base mounted pump o pera t ing instr uct io n s symptoms reasons Pump Fails To deliver • Pump not primed. • Suction line not filled. • Air or vapour pocket in suction line. •...
  • Page 10 Series 4030 i nstal la ti on & Base mounted pump o p era t i n g i n stru ction s symptoms reasons Bearings overheat • Misalignment. • Insufficient cooling to stuffing box. • Badly packed stuffing box. •...
  • Page 11 Series 4030 in sta l l a t io n & Base mounted pump o pera t ing instr uct io n s symptoms reasons Motor overheating • Misalignment. • Speed too high. • Low system friction. • Pumped liquid density is greater than anticipated. •...
  • Page 12 t o r o n t o 23 bertrand avenue toronto, ontario canada, m1l 2p3 +1 416 755 2291 b u f f a l o 93 east avenue north tonawanda, new york u.s.a., 14120 -6594 +1 716 693 8813 b i r m i n g h a m heywood wharf, mucklow hill halesowen, west midlands...