44
Notes on Operation
6.3
Derating
The maximum load depends on the surrounding air temperature.
Table 27: Nominal Values according to UL
IN
OUT
Ambient temp.
Restrictions (derating) apply when the power supply unit is used in applications
that exceed its performance specifications; these are listed below:
Table 28: Deratings
Temperature value
T
> +55 °C
U
Figure 18: Temperature Load Curve
Manual
Version 1.0.0
100 ... 240 VAC; < 0.27 A; 50 ... 60 Hz
24 VDC SELV, 0.5 A
+55 °C
Derating
See figure
−2.6 %/K
"Temperature Load Curve"
Compact Power