20.3 Piping Length Correction Factor

The characteristic of the unit has to be corrected in accordance with the piping length.
20.3.1
CS-RZ25TKR CU-RZ25TKR CS-RZ35TKR CU-RZ35TKR
1.020
1.000
0.980
0.960
0.940
0.920
0.900
3
4
5
1.010
1.000
0.990
0.980
0.970
0.960
3
4
5
Note: The graphs show the factor after added right amount of additional
refrigerant.
6
7
8
9
10
11
12
Piping Length (m)
6
7
8
9
10
11
12
Piping Length (m)
13
14
15
16
17
18
19
13
14
15
16
17
18
19
174
Cooling Capacity
3
1.001
5
1.0000
7.5
0.9793
15
0.9107
20
0.9085
20
Heating Capacity
3
1.006
5
1.0000
7.5
0.9979
15
0.9773
20
0.9675
20