15.2.6
Odor Cut Control
To reduce the odor released from the unit.
Start Condition
o
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
Control content
o
Depends on compressor conditions:
Compressor OFF → Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
Compressor ON → Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.

15.3 Protection Control for Heating Operation

15.3.1
Intake Air Temperature Control
Compressor will operate at limited freq., if indoor intake air temperature is 30°C or above.
15.3.2
Outdoor Air Temperature Control
The Max current value is regulated when the outdoor air temperature rise above 4°C in order to avoid
compressor overloading.
The compressor will be stopped to avoid compressor overloading.
Current Regulated
4°C
Free Within Max Limit
Outdoor air temperature
COMP. ON
-15°C
COMP. OFF
Outdoor
Air
Temperature
105
2°C
-17°C