Summary of Contents for Pilz PNOZ mo5p

  • Page 1 PNOZ mo5p Configurable safety systems PNOZmulti Operating Manual-1001353-EN-05...
  • Page 2 Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
  • Page 3: Table Of Contents

    Download modified project to the PNOZmulti system Section 7 Operation LED indicators Function test of the relay outputs Section 8 Technical details Safety characteristic data Section 9 Supplementary data Service life graph for the relay contacts Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 4 Contents Section 10 Order reference 10.1 Product 10.2 Accessories Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 5: Introduction

    Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ mo5p. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 6 Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 7: Overview Scope

    Plug-in connection terminals (either cage clamp terminal or screw terminal) Max. 8 expansion modules and one fieldbus module can be connected to a base unit. A max. 6 of these may be the expansion modules PNOZ mo5p, PNOZ mo4p, PNOZ mo2p and PNOZ mo1p.
  • Page 8: Safety

    In order to achieve the re- quired safety level for the overall plant/machine, define the safety requirements for the plant/machine and then define how these must be implemented from a technical and organ- isational standpoint. Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 9: Use Of Qualified Personnel

    Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 10: Function Description

    System reaction time Calculation of the maximum reaction time between an input switching off and a linked out- put in the system switching off is described in the document "PNOZmulti System Expan- sion". Block diagram Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 11: Installation

    Damage due to electrostatic discharge! Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm 22,5 94 (3.70") (0.88") Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 12: Connecting The Base Unit And Expansion Modules

    Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 13: Commissioning

    24 (44) single 13 (33) O0 (2) 14 (34) 23 (43) O1 (3) 24 (44) Feedback loop Redundant output Contacts from external contactors 13 (33) O0 (2) 14 (34) 23 (43) O1 (3) 24 (44) Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 14: Connection Example

    Commissioning Connecting the safety valves on a burner in accordance with EN 50156 230 V AC Connection example PNOZ m1p Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 15: Download Modified Project To The Pnozmulti System

    PNOZmulti Configurator. Proceed as described in the operat- ing manual for the base unit. NOTICE For the commissioning and after every user program change, you must check whether the safety devices are functioning correctly. Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 16: Operation

    Start the device again or open the safety contacts (switch off output), so that the internal diagnostics can check the correct opening of the safety contacts for SIL CL 3/PL e at least 1x per month for SIL CL 2/PL d at least 1x per year Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 17: Technical Details

    External contact fuse protection, safety contacts In accordance with the standard EN 60947-5-1 Blow-out fuse, quick Blow-out fuse, slow 6,00 A Circuit breaker 24V AC/DC, characteristic B/C Switch-off delay 50 ms Conventional thermal current 12,0 A Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 18 Horizontal on top hat rail DIN rail Top hat rail 35 x 7,5 EN 50022 Recess width 27 mm Material Bottom PPO UL 94 V0 Front ABS UL 94 V0 Spring-loaded terminal, screw terminal Connection type Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 19 Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals (relay outputs) 10 mm Dimensions Height 94,0 mm Width 22,5 mm 121,0 mm Depth Weight 198 g Where standards are undated, the 2009-01 latest editions shall apply. Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 20: Safety Characteristic Data

    If the service life graphs are not accessible, the stated PFH value can be used irrespective of the switching frequency and the load, as the PFH value already considers the relay's B10d value as well as the failure rates of the other components. Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 21: Supplementary Data

    The service life graphs indicate the number of cycles from which failures due to wear must be expected. The wear is mainly caused by the electrical load; the mechanical load is negli- gible. Switching current (A) Fig.: Service life graphs at 24 VDC and 230 VAC Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 22 To increase the service life, sufficient spark suppression must be provided on all relay con- tacts. With capacitive loads, any power surges that occur must be noted. With DC contact- ors, use flywheel diodes for spark suppression. We recommend you use semiconductor outputs to switch 24 VDC loads. Operating Manual PNOZ mo5p 1001353-EN-05...
  • Page 23 Set spring terminals 1 set of spring-loaded terminals 783 536 Set screw terminals 1 set of screw terminals 793 536 Terminator, jumper Product type Features Order no. PNOZmulti bus terminator Terminator 779 110 KOP-XE Jumper 774 639 Operating Manual PNOZ mo5p 1001353-EN-05...