Inspection Of Parts; Capacitor; Drain Switch - Denso MOVINCOOL Climate pro k18 Service Manual

Table of Contents

Advertisement

INSPECTION OF PARTS

Capacitor

1. Ohmmeter method
Set the ohmmeter to the 10M range. Place the two probes against the two terminals of the
capacitor. At first, the ohmmeter should indicate a small value, and then the reading should
gradually increase towards infinity. This indicates that the capacitor is charging. If the reading
indicates infinity immediately (open) or the ohmmeter fails to move from 0 (short), replace the
capacitor.
2. Capacitance tester
If the tester indicates the capacitance is less than 90% of
the value below, replace the capacitor.
- Voltage: 260VAC
- Rating Capacitance: 45 μF
Always discharge the capacitor before and after testing. If not, it may cause electric shock,
damage to test equipment or malfunction.

Drain Switch

Check for continuity between terminal 1 and terminal 2 when drain switch is pressed.
If continuity does not exist, replace drain switch.
To CN14
WARNING
Terminal 2
Drain Switch
Terminal 1
Top of Base Plate
40