PNOZ mmc12p Configurable compact control systems PNOZmulti Mini Operating Manual-1003192-EN-04...
Page 2
Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
Section 6 Commissioning General wiring guidelines Connecting the supply voltage Interface assignment Download modified project to the PNOZmulti system Connection example Section 7 Operation LED indicators Section 8 Technical Details Section 9 Order reference Product Accessories Operating Manual PNOZ mmc12p 1003192-EN-04...
Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ mmc12p. It is valid until new documenta- tion is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
Page 5
Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ mmc12p 1003192-EN-04...
24 - 127 are used they have different properties (see doc- ument entitled "Communication Interfaces"). Max. 1 PNOZ mmc12p can be connected to the base unit For details of the PNOZmulti Mini base units that can be connected, please refer to the document "PNOZmulti System Expansion".
User Group (EPSG). The central controller (Managing Node) reads input information from the slaves and writes output information to the slaves as part of each cycle. As well as the cyclical transfer of usable data, the expansion module PNOZ mmc12p can also be used for diagnostic and commissioning functions.
Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ mmc12p 1003192-EN-04...
LINK are selected and configured in the PNOZmulti Configurator. The base unit and the fieldbus module PNOZ mmc12p are connected via a jumper. After the supply voltage is switched on or the PNOZmulti control system is reset, the fieldbus module PNOZ mmc12p is configured and started automatically.
NOTICE Damage due to electrostatic discharge! Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm Operating Manual PNOZ mmc12p 1003192-EN-04...
Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ mmc12p 1003192-EN-04...
The power supply must meet the regulations for extra low voltages with protective sep- aration. CAUTION! Only connect and disconnect the expansion module when the supply voltage is switched off. NOTICE When installing, you must refer to the guidelines of the Ethernet POWER- LINKUser Group. Operating Manual PNOZ mmc12p 1003192-EN-04...
PNOZmulti Configurator. Proceed as described in the operat- ing instructions for the base unit. NOTICE For the commissioning and after every program change, you must check whether the safety devices are functioning correctly. Operating Manual PNOZ mmc12p 1003192-EN-04...
When the supply voltage is switched on, the PNOZmulti safety system copies the configur- ation from the chip card. The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base unit. The expansion module PNOZ mmc12p is configured and started automatically. LED indicators Legend LED on...
Page 18
The bus controller is in a PRE_OPERATIONAL_2 state. short Green: 3 x The bus controller is in a READY_TO_OPERATE state. short Green The bus controller is in an OPERATIONAL state. Green The bus controller is in a STOPPED state. Operating Manual PNOZ mmc12p 1003192-EN-04...
In accordance with the standard EN 60068-2-1/-2 Temperature range -25 - 70 °C Climatic suitability In accordance with the standard EN 60068-2-30, EN 60068-2-78 Condensation during operation Not permitted Max. operating height above sea level 2000 m EN 61131-2 Operating Manual PNOZ mmc12p 1003192-EN-04...
Page 20
Torque setting with screw terminals 0,5 Nm Conductor cross section with spring-loaded terminals: Flexible with/without crimp connector 0,2 - 2,5 mm², 24 - 12 AWG Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals 9 mm Operating Manual PNOZ mmc12p 1003192-EN-04...
Page 21
Technical Details Mechanical data Dimensions 100 mm Height Width 22,5 mm Depth 110,4 mm Weight 90 g Where standards are undated, the 2015-08 latest editions shall apply. Operating Manual PNOZ mmc12p 1003192-EN-04...
PNOZ mmcxp 1 pc. Screw terminals Screw terminals, 10 pieces 793 543 PNOZ mmcxp 10 pcs. Terminator, jumper Product type Features Order No. PNOZ mm0.xp connector Jumper yellow/black to connect the modules, 10 piece 779 260 left Operating Manual PNOZ mmc12p 1003192-EN-04...
Page 23
Back cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland +41 62 88979-30 Mexico +43 1 7986263-0...