Parameter
Parameter
S0
Min output
The P.C.B. defines the operating mode and the boiler output according to the combi-
nation of several parameters. The proper operating output of the appliance is defined
S1
Max output
according to the combination of the parameters of menus "n" and "F".
For this reason it is recommended not to alter the parameters of this menu in order not
to compromise the proper operation of the boiler.
S2
Ignition output
In the event of an alteration, anomaly "E62" appears and complete calibration is required.
Id
Parameter
Parameter
Defines the maximum heat output percentage of the boiler during the D.H.W. phase
P0
DHW max
compared to the maximum heat output available
Defines the minimum heat output percentage of the boiler compared to the minimum
P1
Min output
heat output available
Defines the maximum heat output percentage of the boiler during the central heating
P2
Heating max
mode compared to the maximum heat output available
The boiler is set-up for functioning with the relay P.C.B. (optional), which can be
configured
0 = Off
1 = Main zone control
Relay 1
2 =General alarm
P3
3 = CH phase active
(optional)
4 = External gas valve power supply
5 = (Do not use on this boiler model)
6 = (Do not use on this boiler model)
7 = (Do not use on this boiler model)
The boiler is set-up for functioning with the relay P.C.B. (optional), which can be
configured
0 = Off
1 =General alarm
2 = CH phase active
Relay 2
P4
3 = External gas valve power supply
(optional)
4 = Secondary zone control (from TA on relay P.C.B. contact)
5 = Heat pump
6 = (Do not use on this boiler model)
7 = (Do not use on this boiler model)
The boiler is set-up for functioning with the relay P.C.B. (optional), which can be
configured
0 = Off
1 = Chiller remote activation
2 =General alarm
Relay 3
3 = CH phase active
P5
(optional)
4 = External gas valve power supply
5 = heat pump
6 = activation of storage tank pump
7 = Main zone control
8 = (Do not use on this boiler model)
9 = (Do not use on this boiler model).
The pump can function in two ways.
0 intermittent: in winter "mode" the circulator is managed by the room thermostat or by
Pump function-
P6
ing
1 continuous: in "winter" mode the circulator is always powered and is therefore always
If the reading of the external probe is not correct it is possible to correct it in order to
External probe
compensate any environmental factors.
P7
correction
(Over the value of +9 the display shows "CE", which enables an external control function
of the boiler for coupling of the same with a system supervisor)
P8
-
Not used on this boiler model
the remote control
in operation
Description
Description
32
Range
Default
750 ÷ 1700
rpm
According
S0 ÷ 7375
to the boiler
rpm
model
2000 ÷ 4000
rpm
Range
Default
0 - 99 %
99%
0 - P2
0%
according
0 - 99%
to the boiler
model
0 - 7
1
0 - 7
0
0 - 9
0
0 - 1
0
-9 ÷ 9 K
0
-
-