3.10 FLUE TEST.

To define the value to set in the "flue length"
"F0" parameter, detect the parameters during
the "flue test".
To activate this mode, the boiler must be in
"stand-by" mode, which is visible when the
(
) symbol appears.
N.B.: if the boiler is connected to the CAR
"stand-by" function can only be activated via the
remote control panel.
To activate the function, press the "Reset" (2) and
"on/off " (6) buttons simultaneously until func-
tion activation, which is displayed by indicating
the fan operation speed (in hundreds of revs) and
ignition of the flashing "D.H.W. " (8) and central
heating symbols.
Attention: Ensure that the condensate drain
trap has been filled correctly before carrying
out the test.
The appliance remains in this mode for a max-
imum period of 15 minutes, keeping the fan
speed constant.
This function ends once 15 minutes have elapsed,
or by disconnecting supply voltage to the boiler,
or by pressing the "on/off " (6) button for approx-
imately 8 seconds.
Id
Parameter
Parameter
nG
Defines operation with methane gas
G
LG
Defines operation with LPG gas
In the event of an alteration, anomaly "E62" appears and complete calibration is required.
Id
Parameter
Parameter
n
Boiler model
Define the boiler model
Caution: only use the parameter relating to the boiler installed.
In the event of an alteration, anomaly "E62" appears and complete calibration is required.
Check the ΔP between the test pressures (fig. 1-30
Ref. 13), in compliance with the values indicated
in the following table:
Parameter F0
0
1
the
V2
2
N.B.: examinations are carried out by sealing the
holes provided to analyse the flues, making them
pneumatically sealed.
Attention: should there be a boiler malfunction,
you can carry out a flue test to check that there
are no obstructions in the flue system. Different
values to those indicated in the previous tables
indicate a flue system malfunction, especially
a flue system with excessive load losses or ob-
structed system.
3-13
Description
Description
31

3.11 PROGRAMMING THE P.C.B.

The boiler is prepared for possible programming
of several operation parameters. By modifying
these parameters as described below, the boiler
Pressure
can be adapted according to specific needs.
< 145 Pa
To access the programming stage, set the DHW
selector in the "6 o' clock" position and the
146 ÷ 178 Pa
heating selector in the "9 o' clock" position and
press the "Reset" and "Summer/Winter" buttons
179 ÷ 205 Pa
for about 8 seconds (Fig. 3-14).
Once the programming mode has been accessed,
scroll through the five menus (G, P, t, A, F) by
pressing the "Summer / Winter" button for 1
second.
Menu G is reserved for the air-gas control settings
and it features two sub-menus (n and S), relating
to fan and gas valve control settings. Every time
these parameters are altered, the Complete cali-
bration function must be activated (see parag.
3.7). In order to access parameters "n" and "S"
press the "Reset" button sequentially. In order
to exit this part of the menu and access other
parts (categories P, t, A, F) press the "Summer
/ winter" button.
Use the ''D.H.W. regulator'' selector to select
the parameter (within the same sub-menu)
and rotate the ''C.H. regulator'' selector to alter
the value.
Press the "Reset" button for 1 second to store the
altered parameters.
If the parameters are stored successfully, "88"
appears on the indicator (Ref. 14 fig. 2-1) for
2 seconds.
Exit the programming mode by waiting for 15
minutes or by pressing the "Reset" and "Summer/
Winter" buttons at the same time.
3-14
Range
Default
nG
nG
LG
Range
Default
02 = Victrix 24 TT
0 ÷ n
1E