Removable Memory; Troubleshooting - Immergas VICTRIX 24 TT 1E Instruction And Warning Book

Hide thumbs Also See for VICTRIX 24 TT 1E:
Table of Contents

Advertisement

Comando Amico Remoto
: the boiler is
V2
prepared for the application of the Comando
Amico Remoto remote control
(CAR
V2
must be connected to clamps 41 and 44 of the
terminal board (located in the boiler control
panel) respecting the polarity and eliminating
jumper X40.
Room thermostat: the boiler is prepared for the
application of the room thermostat (S20), which
must be connected to clamps 40 and 41 of the
terminal board (located in the boiler control
panel) eliminating jumper X40.
The connector X5 is used for the connection to
the relay board.
The connector X6 is for connection to a personal
computer.
The connector X8 is used for software updating
operations.

3.3 REMOVABLE MEMORY

The P.C.B. is equipped with a removable memory
(2 Fig. 3-4), which records all operation param-
eters and system customisations.
Should the P.C.B. be replaced, you can use the
memory of the replaced board again, so it is not
necessary to reconfigure the appliance.
Attention: replacing the memory must be carried
out after disconnecting all electrical connection
of the P.C.B.
GAS valve SGV 100 B&P
Key:
1 - Gas valve outlet pressure point
2 - Coil
3 - Wiring connector
4 - Gas valve inlet pressure point
P.C.B.
Key:
1 - Fuse 3.15 AF
2 - Removable memory
(A19)

3.4 TROUBLESHOOTING.

N.B.: maintenance interventions must be carried
), which
out by an authorised company (e.g. Immergas
V2
After-Sales Technical Assistance Service).
- Smell of gas. Caused by leakage from gas circuit
pipelines. Check sealing efficiency of gas intake
circuit.
- Repeated ignition blocks. No gas, check the
presence of pressure in the network and that
the gas adduction cock is open. Incorrect
combustion control system calibration, carry
out complete calibration.
- Irregular combustion or noisiness. It may be
caused by: a dirty burner, incorrect combustion
parameters, intake-exhaust terminal not cor-
rectly installed. Check the above components.
- Non-optimal ignition of first ignition of the
burner: even if the burner is perfectly calibrat-
ed, first ignition of the burner (after calibration)
can be sub-optimal; the system automatically
regulates ignition until it finds optimal ignition
of the said burner.
- Frequent interventions of the overheating
safety thermostat. It can depend on the lack
of water in the boiler, little water circulation
in the system or blocked pump. Check on the
manometer that the system pressure is within
established limits. Check that the radiator
valves are not closed and also the functionality
of the pump.
- Drain trap clogged. This may be caused by
dirt or combustion products deposited inside.
Check that there are no residues of material
blocking the flow of condensate.
- Heat exchanger clogged. This may be caused by
the drain trap being blocked. Check that there
are no residues of material blocking the flow of
condensate.
- Noise due to air in the system. Check opening
of the special air vent valve cap (Part. 20 Fig.
1-30). Make sure the system pressure and
expansion vessel pre-charge values are within
the set limits; The factory-set pressure values of
the expansion vessel must be 1.0 bar, the value
of system pressure must be between 1 and 1.2
bar.
- Noise due to air inside the condensation
module. Use the manual air vent valve (Part.
11 Fig. 1-30) to eliminate any air present in the
condensation module. When the operation has
been performed, close the manual vent valve.
- Poor production of D.H.W. If a drop in per-
formance is detected during supply of D.H.W.,
it is possible that the condensation module
or D.H.W. heat exchanger is clogged. In this
case, contact Immergas After-Sales Assistance
Service that has procedures to clean the module
or D.H.W. heat exchanger.