Si281311
2. Procedure to Remove Propeller Fan and Fan
Motor
Procedure
Step
Remove the front panel 2,
following the procedure
indicated at "Procedure to
Remove Outside Panels
and Related Parts".
1. Remove the propeller fan
Remove the 4 screws
1
that fix the discharge
grille. Remove from 4
hooks at upper and
lower side and then
remove the discharge
grille.
Remove the fan setting
2
nut that fixes the
propeller fan.
∗ Remove the top
3
panel, following the
procedure indicated
at "Removal of
Outside Panels and
Related Parts".
2. Remove the fan motor
Remove the connector
1
for the fan motor from
the printed wiring board
(PWB).
2
Remove the 3 clamps
which fix the lead wire.
(3 hooks of partition
plate)
Remove the 3 screws
3
of the front panel and
then pull lead wire
frontward.
Pull out the fan motor,
4
after removing the 4
fixing bolts.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Propeller fan
Hooks
Fan setting nut
Hooks
Discharge grille
Connector for fan motor (X106A)
Clamp
4 bolts

Procedure to Remove Propeller Fan and Fan Motor

In case of removing the
connector, do not pull the
lead wire. Hold the
connector part and press the
hook.
Lead wire
Precaution for the motor
installation
Be sure to fix the lead wire of
the motor. Otherwise the
lead wire might be entangled
with the motor and causes
failure.
Points
Propeller fan
3