Procedure To Remove Switch Box - Daikin RZQ71KBV1 Service Manual

Removal procedure, 3 hp class, outdoor unit, inverter, pair type
Hide thumbs Also See for RZQ71KBV1:
Table of Contents

Advertisement

Procedure to Remove Switch Box

3. Procedure to Remove Switch Box
Procedure
Step
Remove the front panel,
the suction grille, the top
panel, the side panel, and
the piping cover, following
the procedure indicated at
"Procedure to Remove
Outside Panels and
Related Parts".
Remove the wirings to
1
the switch box and the
related parts
Remove the
connectors below;
• Fan motor
(X106A)
• Pressure sensor
(X17A)
• Coil of four way
valve (X25A)
• Compressor relay
(X502A)
Remove the parts
below;
• Electronic
expansion valve
(Y1E)
• Liquid pipe
thermistor (R6T)
• Suction pipe
thermistor (R3T)
• Discharge pipe
thermistor (R2T)
• Outdoor air
thermistor (R1T)
• Heat exchanger
thermistor (R4T)
• Intermediate heat
exchanger
thermistor (R5T)
∗ When removing, cut
the clamps that fix
each lead wire of
each part.
2
Removing the switch
box
Remove 2 screws
that fix the switch
box
Holding the switch
box, lift upward and
remove the 2 hooks
(1 right and 1 left)
and then pull out.
4
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Fan motor (X106A)
For
pressure
sensor
(X17A)
For four way
valve coil
(X25A)
For compressor
relay (X502A)
R6T
Hook
R1T
R2T
Precaution for the
R3T
installation of the switch box:
After restoring each part, fix
each lead wire with the
clamps in the same way as
originally fixed.
R5T
R4T
Y1E
Hook
Fixing screws
Si281311
Points
Removal Procedure

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzq71kbv4aRq71kbv4a

Table of Contents