Graphics, texts and variables to be displayed must be positioned such that they fit properly into the display unit. Page 6 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
8 lines are simply not visible at a module with 8 pixel lines. The following example depicts a module with 64 x 16 pixels including three different character heights: Page 8 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
The display unit then waits for valid output data from the user (via the interface). Page 9 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
“Factory Settings of internal Interface”. Enter “0” (server configuration). Enter the desired IP address and press the enter key. Page 10 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Page 11
From now on, the control frame can be transmitted to the display via the selected IP address and the selected port. Page 11 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
“online character”. As a rule, a pause of „receiving timeout“ + 150 ms between frames is sufficient. Page 12 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
LEN-H und LEN-L only need to be transmitted if a checksum is used. If bit 1 in the FC byte is not set, LEN-H and LEN-L may not be transmitted! Page 13 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
4 through 7 must be set (1) CHK-L: Low nibble for checksum: bits 3 through 0, bits 4 through 7 must be set (1) Page 14 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
... must be transmitted for position 123 (ASCII characters “1”, “2” and “3”). Refer to chapter “Displayable Characters” for a table of displayable ASCII characters! Page 15 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Existing character sets are overwritten with the new character sets if a new configuration is downloaded to the display unit! Page 16 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
(from the last “ESC-A” frame)! Black is used if the background colour has been set to transparent! Page 18 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Variable content is stored to RAM only. After the device has been switched off and back on again, the variables are returned to their pre- configured values. Page 19 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Variable positioning is stored to RAM only. After the device has been switched off and back on again, the variables are returned to their pre- configured positions. Page 20 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Page 22
If the minimum limit is fallen short of or the maximum limit is exceeded, a blinking marker appears at the respective limit. Page 22 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Page 23
The background colour used for variables may not be transparent, and a character set with uniform character width should be used in order to assure correct display. Page 23 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
“0” – “9” The perimeter of the rectangle is drawn with the foreground colour. The rectangle is filled with the background colour. Page 25 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
The Y positions of the first and last pixel lines within the scrolling range define the start and end lines (end line > start line!). Only the last selected scrolling range is used! Page 26 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
The y position of the first and last pixel lines within the scrolling range define the start and end lines (end line > start line!). Only the last selected scrolling range is used! Page 27 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
“0” – “9” Within a range of 0 to 100% for each of the following colours: “1” = green “2” = red Page 28 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
The output bits are used to switch the digital outputs (if included). After switching the device on, all outputs are cleared (0). Page 29 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Execution starts with the indicated macro. Skipping is also possible during macro execution through the use of this command within a macro sequence. Page 30 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
100 ms happens and the digital inputs are read in again. Page 31 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Page 32
100 ms), for example during the delay time (1 second). If Input 2 is set, the display is cleared. Page 32 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
This sequence can be used as part of a macro, as well as part of a receive frame. Page 33 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
(“reading out decimal point from the display”, “digital inputs and outputs”). The error code in the response frame always relates to the last partition frame. Page 34 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
=> An “online text” with character set 1, on cursor position x=2, y=3 with foreground colour „yellow“ and background colour „black“ is displayed (blinking). Page 35 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
3.11.2 Input Level at the Parallel Inputs Level Voltage Range U (low) + 0 to 1.6 V DC U (high) + 18 to 30 V DC Page 37 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Strobe (rising edge, 0 to 1: apply value now) For example, the following assignments are used to display text 12: 16 15 14 13 12 11 10 Page 38 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Strobe (rising edge, 0 to 1: apply value now) For example, the following assignments are used to clear graphic 7: 16 15 14 13 12 11 10 Page 39 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
3 (fourth digit). The inputs must be set up as follows to this end: 16 15 14 13 12 11 10 Page 40 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Note: The two outer pins at the Ethernet socket are not used (see above drawing for identification of pin 1). Page 42 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Page 43
Relay 2, normally open, b n.c. Relay 1 / 2 is controlled by digital output 1 / 2 (frame: ESC+“D”, optionally expandable). Page 43 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
Page 44
Please refer to chapter “Parallel Interface” for details concerning the parallel inputs. Page 44 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
*Carriage Return: The cursor jumps to the beginning of the next line. Any Windows character set, as well as any user defined character set can be used. Page 46 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
If any changes have been done, press “9” (Save and exit) to save all settings. -> The Telnet connection is interrupted. Page 47 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
“as is”. No guarantee claims may be made in such cases. The General Terms and Conditions of microSYST Systemelectronic GmbH in current version apply as well. Page 50 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...
migra MPB 5.00 10/20/16 5.10 11/13/17 Change of address and title MPB Certified per DIN EN ISO 9001. Page 51 microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach +49 9681 91960-0, +49 9681 91960-10, info@microsyst.de, www.microsyst.de...