Requirements for Cabling Indoors
When cabling indoors, keep a certain distance away from the devices that may cause
high-frequency interferences, such as down-conductor cable, powerline, power
transformer and electromotor.
The main cable should be paved in the metal raceway of the access shaft. When
cabling, keep the loop area formed by the cable itself as small as possible.
Requirements for the distance between Ethernet cable and other pipelines are shown
in the table.
Other Pipelines
Down-conductor
PE
Service pipe
Compressed air pipe
Thermal pipe (not wrapped)
Thermal pipe (wrapped)
Gas pipe
The two diagrams below demonstrate parallel net length and parallel-overlapping
net height.
Note:
The above minimum net length/height is required when metal raceway is not
used. If any requirements cannot be met, you can add a steel tube or metal
raceway for shielding.
Requirements for the distance between Ethernet cable and high-power electric devices
are in following tables.
Cable
Pave Way
Parallel cabling
<2kVA
One is in the grounded metal raceway or metal pipe
powerline
The both are in the grounded metal raceway or
metal pipe
Ethernet Cable
Min Parallel Net Length
L (mm)
1000
50
150
150
500
300
300
10/100Mbps Unmanaged Switch
Min Parallel-overlapping
Net Height H (mm)
300
20
20
20
500
300
20
Min Parallel
Length (mm)
130
70
10
Lightning Protection
11