8. Installation details
8.1
Wrench torque sheet for installation
Outside diameter
mm
inch
1/4
φ6.35
3/8
φ9.52
1/2
φ12.7
8.2
Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
7K
9K
2
mm
1.0
1.0
8.3
Pipe length and the elevation
Pipe size
Capacity
Btu/h
GAS
07k~09K
3/8'' (φ9.52)
12K
1/2'' (φ12.7)
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be install per 5-7 meters.
13
Service manual
Torque
Kg.m
1.8
4.2
5.5
12K
1.5
LIQUID
1/4'' (φ6.35)
1/4'' (φ6.35)
Standard
Max.
length
Elevation
(m)
B (m)
5
5
5
5
Max.
Additional
Pipe
refrigerant
length
(g/m)
A (m)
10
30
10
30
In case that
more than