11.5.2 OFF Timer Control
OFF timer can be set using remote control, where the unit with timer set will stop at set OFF time.
Notes:
1
By pressing ON/OFF operation button, the ON Timer or OFF Timer setting will not be cancelled.
2
To cancel the previous timer setting, press CANCEL button.
3
To activate the previous timer setting, press SET button.
4
If main power supply is switched off, the Timer setting will be cancelled.

11.6 Random Auto Restart Control

When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes. There are 10 patterns to be selected randomly after power supply resumes.
This control is not applicable during OFF/ON Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.

11.7 Indication Panel

LED
Color
Light ON
Light OFF
Note:
If POWER LED blinks, the possible operation of the unit is operation mode judgment, or ON timer sampling.
If TIMER LED blinks, there is an abnormal operation occurs.
POWER
Green
Operation ON
Timer Setting ON
Operation OFF
Timer Setting OFF
TIMER
Orange