TABLE A3 - Control Board Connector Descriptions (Bottom)

Name
Description
GND
BACnet MS/TP
B
BACnet MS/TP
A
BACnet MS/TP
STAGE1
Compressor Stage 1
STAGE2
Compressor Stage 2
RV_#1
Reversing Valve #1
RV_#2
Reversing Valve #2
SOL#1
Solenoid#1 (NC#1)
SOL#2
Solenoid#2
24VAC
Power supply for board
COM
Power supply for board
AI_5
Analog In Channel 5
AI_4
Analog In Channel 4
AI_3
Analog In Channel 3
AI_2
Analog In Channel 2
AI_1
Analog In Channel 1
AI_0
Analog In Channel 0
GND
Ground pin
GND
Ground pin
5VDC
Power for analog sensors
12VDC
Power for analog sensors
24VDC
Power for analog sensors
A
MODBUS
B
MODBUS
GND
MODBUS
ISSUE 03: 1-Oct-2021
Ground for shield if required.
RS-485 for BACnet communication.
RS-485 for BACnet communication.
Starts / stops the compressor.
Not used.
Off in pool heat mode, energized in air reheat or heat rejection modes.
Off in pool heat mode or air reheat modes, energized in heat rejection mode.
Off in pool heat mode or air reheat modes, energized in heat rejection mode.
Not used.
24VAC power for control board.
GND for control board.
Optional pool water external sensor (type 3 or 7 10k thermistor).
0 to 5VDC or 4-20mA user settable with board jumper.
0 to 5VDC or 4-20mA user settable with board jumper.
0 to 5VDC or 4-20mA user settable with board jumper.
0 to 5VDC or 4-20mA user settable with board jumper.
Optional compressor current sensor.
Ground for analog sensors.
Ground for analog sensors.
5VDC power supply for sensors.
12VDC power supply for sensors.
24VDC power supply for room sensor/user interface (room thermostat).
RS485 communication for room sensor/user interface (room thermostat).
RS485 communication for room sensor/user interface (room thermostat).
Ground for shield if required.