TABLE 24 - BACnet OBJECTS - ALARM Descriptions (Read Only)

Name
Data Type
AI0 (Comp1 Current)
Analog Input
AI1 (Comp2 Current)
Analog Input
LPS1
Analog Input
HPS1
Analog Input
LPS2
Analog Input
HPS2
Analog Input
Outdoor Flow
Binary Value
Indoor Flow
Binary Value
Phase Monitor1
Binary Value
Phase Monitor2
Binary Value
Comp Monitor1
Binary Value
Comp Monitor2
Binary Value
Name
Permanent Alarms 1
(Present Value)
Permanent Alarms 2
(Present Value)
Note: Permanent Alarm objects are type Analog Value but values are bit coded and may be decoded as such (integer value).
Note * : Value is for a single alarm and reference only. Value includes + 1 for Master Alarm
Note: Objects may be subject to change without prior notice.
ISSUE 03: 1-Oct-2021
ID
AI0
Stage 1 Status alarm (Start / Stop Failure) - requires accessory
AI1
N/A
AI6
Low pressure alarm
AI7
High pressure alarm
AI13
N/A
AI14
N/A
BV10 N/A
BV11 N/A
BV12 Phase Monitor alarm - requires accessory
BV13 N/A
BV14 N/A
BV15
N/A
DECIMAL
ID
BIT #
VALUE*
AV6
-
-
0
1
1
3
2
5
3
9
4
17
5
33
6
65
7
129
8
257
14
16,385
15*
32,769
AV7
-
-
Description
Bit description is given below.
Master permanent alarm (occurs when any alarm occurs)
Low pressure heating mode alarm (suction pressure)
Low pressure cooling mode alarm (suction pressure)
High pressure heating mode alarm (discharge pressure)
High pressure cooling mode alarm (discharge pressure)
Loss of charge alarm
Phase monitor alarm - requires accessory
Compressor monitor alarm - N/A
Status alarm - N/A
N/A
N/A
N/A