TABLE 23 - BACnet OBJECTS - DATA (Read Only)

Name
AI0 (Comp1_Current)
AI1 (Comp2_Current)
AI2
AI3
AI4
AI5 (HTS)
LPS1
HPS1
EVAP1
COND1
Suction Line 1
Superheat 1
EEV1 Position
LPS2
HPS2
EVAP2
COND2
Suction Line 2
Superheat 2
EEV2 Position
Outside Ambient
O_IN
O_OUT
I_IN
I_OUT
PWM_IN
PWM1 (OD Fan)
PWM2
PWM3 (OV2)
PWM4 (IV2)
Operation Mode
STAGE1
STAGE2
ICR (Indoor Circ)
DO0 (OV1)
DO1 (IV1))
DO2 (HYD_AUX)
DO3 (AUX_ONLY)
PHS1
PHS2
CONTROLS (LOC/REM)
Outdoor Flow
Indoor Flow
Phase Monitor1
Phase Monitor2
Comp Monitor1
Comp Monitor2
Note: available objects may be subject to change without prior notice.
ISSUE 03: 1-Oct-2021
ID
Property
Data—Type Analog Input
AI0
Present Value
AI1
Present Value
AI2
Present Value
AI3
Present Value
AI4
Present Value
AI5
Present Value
AI6
Present Value
AI7
Present Value
AI8
Present Value
AI9
Present Value
AI10
Present Value
AI11
Setpoint Value
AI12
Present Value
AI13
Present Value
AI14
Present Value
AI15
Present Value
AI16
Present Value
AI17
Present Value
AI18
Setpoint Value
AI19
Present Value
AI20
Present Value
AI21
Present Value
AI22
Present Value
AI23
Present Value
AI24
Present Value
Data Type—Analog Value
AV0
Present Value
AV1
Present Value
AV2
Present Value
AV3
Present Value
AV4
Present Value
AV5
Present Value
Data Type—Binary Output
BO0
Present Value
BO1
Present Value
BO2
Present Value
BO3
Present Value
BO4
Present Value
BO5
Present Value
BO6
Present Value
BO7
Present Value
BO8
Present Value
Data Type—Binary Value
BV9
Present Value
BV10
Present Value
BV11
Present Value
BV12
Present Value
BV13
Present Value
BV14
Present Value
BV15
Present Value
Units
Amps
Compressor current draw (AI0) - requires accessory
User
User defined (0-5VDC or 4-20mA)
User
User defined (0-5VDC or 4-20mA)
User
User defined (0-5VDC or 4-20mA)
User
User defined (0-5VDC or 4-20mA)
degF (degC)
Pool water temperature from ext. sensor - requires accessory
PSIG (kPa)
Low pressure value (suction pressure)
PSIG (kPa)
High pressure value (discharge pressure)
degF (degC)
Evaporating Temperature
degF (degC)
Condensing Temperature
degF (degC)
Suction line temperature
degF (degC)
Superheat
%
EEV1 position (% open)
PSIG (kPa)
N/A
PSIG (kPa)
N/A
degF (degC)
N/A
degF (degC)
N/A
degF (degC)
N/A
degF (degC)
N/A
%
N/A
degF (degC)
N/A
degF (degC)
N/A
degF (degC)
N/A
degF (degC)
N/A
degF (degC)
Pool water temperature (physically located on water IN pipe)
%
PWM input (from external source)
%
AC2 Outdoor Fan speed (if AC2 present)
%
PWM output value (spare)
%
PWM output value (spare)
%
PWM output value (spare)
N/A
Unit operation mode - refer to Operation Mode Table
N/A
Compressor contactor
N/A
N/A
N/A
Pool water pump control
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Control Indicator, 0 = Local (manual override), 1 = Remote
N/A
N/A
N/A
N/A
N/A
Phase Monitor Stage 1 - requires accessory
N/A
N/A
N/A
N/A
N/A
N/A
Page 41