Table 25 - Bacnet Objects - Fault Descriptions (Read Only) - Maritime Geothermal Nordic PC Series Installation And Service Manual

Table of Contents

Advertisement

TABLE 25 - BACnet OBJECTS - FAULT Descriptions (Read Only)

Name
Data Type
AI4
Analog Input
AI5 (Hot Tank)
Analog Input
LPS1
Analog Input
HPS1
Analog Input
LPS2
Analog Input
HPS2
Analog Input
Suction Line1
Analog Input
Suction Line2
Analog Input
Outside Ambient
Analog Input
O_IN
Analog Input
O_OUT
Analog Input
I_IN
Analog Input
I_OUT
Analog Input
Name
ID
Board Faults
AV8
Sensor Faults
AV9
Note: Board and Sensor Fault objects are type Analog Value but values are bit coded and may be decoded as such (integer value).
Note * : Value is for a single fault and reference only.
Note: Objects may be subject to change without prior notice.
ISSUE 03: 1-Oct-2021
ID
AI0
N/A
AI1
External pool water temperature sensor faulty or disconnected - requires accessory
AI6
Low pressure sensor faulty or disconnected
AI7
High pressure sensor faulty or disconnected
AI13
N/A
AI14
N/A
AI10
Suction line 1 temperature sensor faulty or disconnected.
AI17
N/A
AI20
N/A
AI21
N/A
AI22
N/A
AI23
N/A
AI24
Internal pool water temperature sensor faulty or disconnected.
DECIMAL
BIT #
VALUE*
-
-
Bit description is given below.
0
1
Digital inputs
1
2
Digital outputs
2
4
PWM outputs
3
8
Analog to digital conversion
4
16
Real time clock
5
32
EEPROM memory
6
64
Menu buttons
7
128
LCD Display
-
-
Indicates sensor failures. Bit description is given below.
0
1
Suction line 1 temperature
1
2
N/A
2
4
Outdoor Ambient temperature - requires accessory
3
8
Calibration temperature
4
16
N/A
5
32
Internal pool water temperature sensor
6
64
N/A
7
128
N/A
8
256
N/A
9
512
N/A