oventrop OV-DMC 2 Operating Instructions Manual page 23

Table of Contents

Advertisement

Enter nominal flow rate
for valve no. 1 (e.g. 500
l/h).
Go to next menu win-
dow by using the key
"OK".
The command for
storing appears.
Go to next menu win-
dow by using the key
"OK".
User information.
Set back valve to previ-
ous presetting (e.g. 3.0).
Go to next menu win-
dow by using the key
"OK".
Display of the next valve
(2) which can be measu -
red in the regulating
group. Other valves
may also be chosen
be means of the
keys
and
.
The numbering of valves
once determined must
be observed.
Go to next menu win-
dow by using the key
"OK".
OV-BALANCE
---------------------
---------------------
in object
Cellar
G.: 1 / 1
Hydrocon R DN 20
3.0 preset'g 0.0
mbar
500 l/h
>STORE<
OV-BALANCE
---------------------
---------------------
in object
Cellar
G.: 1 / 1
Hydrocon R DN 20
3.0 preset'g. 0.0
mbar
500 l/h
>STORE<
OV-BALANCE
---------------------
---------------------
in object
Attention
3.0
reset valve
OV-BALANCE
---------------------
---------------------
in object
Cellar
G.: 1 / 2
----------- DN 00
3.0 preset'g. 0.0
mbar
l/h
>STORE<
OV-Balance
Measurement
23