Technical Data; Analog Input - nVent RAYCHEM TCONTROL-05 Manual

Panel mounted controller
Table of Contents

Advertisement

5.

Technical data

5.1

Analog input

Thermocouples
Designation Type
Fe-CuNi
Fe-CuNi
Cu-CuNi
Cu-CuNi
NiCr-Ni
NiCr-CuNi
NiCrSi-NiSi
Pt10Rh-Pt
Pt13Rh-Pt
Pt30Rh-
Pt6Rh
24 | nVent.com/RAYCHEM
Standard
"L"
DIN 43710
(1985)
"J"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"U"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"T"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"K"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"E"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"N"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"S"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"R"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
"B"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS
Measuring
range
IPTS-68 –200 to
+900°C
ITS-90
–210 to
+1200°C
IPTS-68 –200 to
+600°C
ITS-90
–270 to
+400°C
ITS-90
–270 to
+1300°C
ITS-90
–270 to
+1000°C
ITS-90
–270 to
+1300°C
ITS-90
–50 to
+1768°C
ITS-90
–50 to
+1768°C
ITS-90
–50 to
+1820°C
Accuracy
a
≤ 0.25 %
≤ 0.25 % from
-100°C
≤ 0.25 % from
-100°C
≤ 0.25 % from
-150°C
≤ 0.25 % from
-80°C
≤ 0.25 % from
-80°C
≤ 0.25 % from
-80°C
≤ 0.25 % from
20°C
≤ 0.25 % from
50°C
≤ 0.25 % from
400°C