Error Messages; Further Information - nVent RAYCHEM TCONTROL-05 Manual

Panel mounted controller
Table of Contents

Advertisement

4.3

Error messages

Display
<<<<
>>>>
----
Depends on the signal type (measuring probe); see chapter
a
"Technical data". In the event of an error, the controller switches
to manual mode.
4.4

Further information

For further information regarding the operation and configuration
of the device, see the operating manual, as well as the interface
description (Modbus) and the ST editor manual, if necessary.
chapter 1.9 "Available technical documentation", Page 10
Ethernet interface (option)
The settings of the Ethernet interface must be made with the
Lantronix CPR Manager PC software from the manufacturer
Lantronix, Inc. Configuration on the device or with the setup
program is not necessary.
Further information can be found in the interface description
(Modbus).
Possible cause
a
Measuring range
underflow
Short-circuit (probe/line)
Break (probe/line)
Polarity
Measuring range overflow
Break (probe/line)
Polarity
Measures
Check sensor and line
(break, short- circuit,
polarity)
Check connection
terminals
Check configuration
(signal type, linearization,
resistance measuring
range, scaling)