ABB REL300 Instruction Manual page 173

Hide thumbs Also See for REL300:
Table of Contents

Advertisement

Table B-1: Present REL300 Settings (Pilot System) - V2.7x
VERS
0
OSC
TRIP
FDAT
TRIP
CTR
1000
VTR
2000
FREQ
60
CTYP
5
RP
NO
XPUD
.5
DTYP
KM
TTYP
OFF
62T
5.000*
PTRI
YES
Z1RI
YES
Z2RI
NO
Z3RI
NO
BFRB
NO
PLT
NO
STYP
3ZNP
FDGT
0
WFEN
NO
3TRM
NO
BLKT
0
PLTP
OUT
PLTG
6.00
Z1P
4.5
Z1G
4.5
T1
0
Z2P
OUT
T2P
1.00
Z2G
OUT
T2G
1.50
NOTE:
This REL300 settings table is for 60 Hz and 5A ct systems. For 1A ct, change PLT, PLG,
Z1P, Z1G, Z2P, Z2G, Z3P, Z3G, RT, RU by multiplying a factor of 5, and all current val-
ues mentioned in the text should be multiplied by a factor of 0.02.
Curve #
CO2
CO5
CO6
CO7
CO8
CO9
CO11
* For Single Pole Trip option only.
Table B-2. Trip Time Constants For Co Curves
T
0
111.99
735.00
8196.67
13768.94
784.52
671.01
524.84
3120.56
477.84
4122.08
310.01
2756.06
110.
17640.00
K
C
0.675
1.13
1.19
0.08
1.27
1.35
0.5
I.L. 40-385.7
Z3P
OUT
T3P
2.00
Z3G
OUT
T3G
2.50
Z3FR
FWD
PANG
75
GANG
75
ZR
3.0
LV
60
IL
0.5
IM
1.0
IOS
0.5
IOM
1.0
ITP
OUT
ITG
OUT
OSB
NO
OSOT
4000
RT
15.00
RU
15.00
DIRU
ZSEQ
GBCV
OUT
GBPU
0.5
GTC
24
GDIR
YES
CIF
OUT
LLT
NO
LOPB
NO
LOIB
NO
AL2S
NO
SETR
YES
TIME
NO
P
R
1
501
1
22705
1
1475
1
2491
1
9200
1
9342
2
8875
B-11

Advertisement

Table of Contents
loading

Table of Contents