Repeat AG fault and measure the trip time, which should be < 2 cycles. Change the setting of
T1 from 0 to 2. Repeat the test; the trip time should extend for an additional 2 cycles. Reset T1
to zero.
The following formula can be used when PANG
or
or
where
or
Example:
This is the trip current (4.3A) at the maximum torque angle of -57.76° (current lags voltage by
57.76°).
The following equation should be used for the angle of x on the MHO circle:
A-4
Vxg
=
(I
+ K
I
) Zcg
0
0
X
K
I
0
x
Vxg
=
I
+
----------- -
x
3
V
xg
I
=
----------------------------- -
X
K
Z
1
+
------
cg
(
Z
Z
oL
1L
K
=
---------------------------- -
0
Z
1L
(
=
Z
GANG PANG
R
I
=
--------------------------------------------------------------------------------------------------------- -
X
jPANG
Z
e
cg
I
=
---------------------------------------------------------------------------------------- -
X
2
jPANG
-- - Z
e
cg
3
Vag
=
30
Z1g = 4.5
GANG = 40
Ia
=
------------------------------------------------------------------ -
2
(
)e
j85
-- - 4.5
3
=
------------------------------------------------------------------------------------------------------------------------------
(
3
cos
85
– (
=
4.31
57.76
GANG:
Zcg
o
3
)
) -1
V
xg
(
j GANG PANG
Zr e
1
+
----------------------------------------------------------- -
3
V
xg
1
jGANG
+
-- - Z
Z r e
cg
3
PANG = 85
Zr = 3
30
1
(
) 3 ( )e
j40
+
-- - 4.5
3
30
)+ j 3 sin (85) + 4.5 cos (40) + j4.5 sin (40)
)
)
1