This Completes the Opto-Input Hardware Test.
Step 37.
1.1.2
PILOT PERFORMANCE TESTS
To prepare the REL300 relay assembly for Pilot Acceptance Tests, connect the REL300 per
Figure B-1, Configuration 1 (Page B-6) sub 13 or higher, three Reed relays are used to replace
the mercury relays for GS, Carrier STOP and SEND. Check jumpers JMP1 (STOP) and JMP2
(SEND) for NO or NC output contact selection.
1.1.2.1
Front Panel Check
Step 1.
Step 2.
• PLT
• Z3FR REV
• ZIP
• ZIG
• PLGF 6.0
• PLGR
NOTE:
When the dc voltage is applied to TB5 terminals, check jumper position on Intercon-
nect module for the appropriate selection.
Connect a rated dc voltage to PLT/ENA terminals TB5/9(+) and TB5/10(-).
Change the LED mode to "TEST" and select the function field to OPTI. Apply a rat-
ed voltage to TB5 appropriate terminals and a non-zero HEX value should be
shown on the right-hand side display as follows:
Term
(TB5)
7(+), 8
11(+), 12
9(+), 10
13(+), 14
1(+), 2
3(+), 4
5(+), 6
* Optional
This completes the basic Acceptance Test for the REL300 Non-Pilot system. (See
subsequent segment for optional Single Pole Trip and Out-of-Step Block tests.)
Repeat steps 1 thru 6 in Non-Pilot Acceptance Tests.
Change the value settings, in Table A-1, as follows:
YES
PLTP
Z3P
OUT
Z3GF
OUT
• Z3GR
• T3P
0.01
• T3G
Function
(OPTI)
RCVR-1 *
RCVR-2 *
PLT-ENA *
SBP
52a *
52b
EXT-RST
6.0
• PTRI
6.0
6.0
0.01
BLK
BLK
I.L. 40-385.7
Value
(HEX)
01
02
04
08
10
20
40
YES
A-17