FUME HOOD ACCESSORIES

Cava™ can take advantage and multiple fume hood accessories to
effectively monitor and control fume hood face velocity, reduce
energy consumption, and keep work environments safe.
Fume hood accessories provided by Antec Controls include:
1.

Fume Hood Valve Module (FVM) - Venturi Valve (VV) Applications

2.
Fume Hood Valve Module (FVM) - Venturi FX Valve (VFX) and
Terminal Unit (TU) Applications
3.
Sash Position Sensor (SPS)
4.
Sidewall Velocity Sensor (SVS)
5.
Fume Hood Presence Sensor (FPS)
Fume Hood Valve Module (FVM) - Venturi Valve (VV) Applications
The Fume Hood Valve Module (FVM) works directly with Cava™ to accurately meet
the required exhaust airflow and fume hood face velocity. The FVM used in Venturi
Valve applications uses calibrated position feedback to provide accurate airflow
through the valve and provides real-time differential pressure readings to ensure the
valve remains within its operating parameters at all times. The FVM delivers this
real-time airflow device information to Cava™ for display and communication over
CANbus.
See the FVM product submittal on
Dimensions, and Wiring.
Mechanical Installation
A
B
C
9 | CAVA – Manual |
AntecControls.com
AntecControls.com
for Specifications,
Overview
The FVM is factory calibrated and mounted on the valve with which it was ordered. Only
electrical installation is required. Open the controls enclosure on the valve and follow the
wiring diagram in the project submittals for electrical installation.
Components
D
A
4 Analog Outputs (0 to 10 VDC, 10 mA Max. Each connected actuator requires 1 output)
E
B
2 Potentiometer terminals (unique to Venturi Valve applications)
C
Terminal Block to be connected to 24VAC power source (50/60 Hz, 17 VA Max)
D
High-pressure port
F
E
Low-pressure port
F
Indicator LED
G
G
CANbus terminal for connection to CAVA and other CANbus devices
H
H
Fume Hood Valve Module (FVM) pre-installed in fume hood valve enclosure
NOTE:
The FVM is factory mounted within the enclosure using #8 x 5/16 in. screws through
three mounting holes.
NOTE:
The maximum torque rating for any bushings on the enclosure is 4.43 in·lbs (0.5 N·m).
CAUTION
Different types of fume hood accessories
can be used with Cava™. When using
accessories by Others, ensure that the
output from or input to the device meets
the requirements of the inputs and outputs
on Cava™ which can be found on
CAVA - MANUAL
Page
1.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents