Network Architecture Summary

See the information outlined in the example below for a summary of the network architecture of Cava™.
Typical Laboratory Wiring
Line Color
Network Type
Blue
Room Information Network (RIN)
Green
Controller Area Network (CAN)
Red
BACnet MS/TP
8 | CAVA – Manual |
AntecControls.com
Considerations
Up to 24 controllers (PACE and CAVA combined), with a maximum of 16 CAVAs
Daisy chained network wiring between each device on the network
NOTE:
A connection through a RIN access point is used to start-up and commission the
system. An Ethernet Port on the back of any CAVA can act as this access point.
Maximum of 3 Sidewall Velocity Sensors (SVS)
Maximum of 1 Fume Hood Valve Module (FVM)
Daisy chained network wiring between each device on the network
Recommended up to 32 devices (including CAVA, PACE, PMT, MVM, or 3rd party)
One BACnet network is allowed per RIN
Daisy chained MS/TP segment only connects through one PACE (or CAVA if no PACE is
present) controller per room