Physical Data - Bryant PURON 583B User Manual

Single-package gas heating/electric cooling units
Table of Contents

Advertisement

UNIT SIZE 583B
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb)
COMPRESSORS
Quantity
REFRIGERANT (R-410A)
Quantity (lb)
REFRIGERANT METERING DEVICE
Orifice ID (in.) AccuRater® Piston
CONDENSER COIL
Rows—Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows—fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Hp (Rpm)
EVAPORATOR BLOWER (ICM FIOP ONLY)
Nominal Airflow (Cfm)
Size (in.)
Motor Hp (Rpm)
FURNACE SECTION
Burner Orifice No. (Qty...Drill Size)
Natural
Burner Orifice No. (Qty...Drill Size)
Propane
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto.)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto.)
RETURN-AIR FILTERS (in.)
Throwaway

PHYSICAL DATA

024040
024060
030040
2
2
2-1/2
290
290
313
5.0
5.0
5.5
.057
.057
.057
1/17
1/17
1/17
10.9
10.9
12.7
2350
2350
2350
22
22
22
1/8 (825)
1/8 (825)
1/8 (825)
3/15
3/15
3/15
3.7
3.7
3.7
800
800
1000
10 x 10
10 x 10
10 x 10
1/4 (1075)
1/4 (1075)
1/4 (1075)
800
800
1000
10 x 10
10 x 10
10 x 10
1/2
1/2
1/2
2...44
2...38
2...44
2...50
2...46
2...50
20 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 1 24 x 30 x 1 24 x 30 x 1
—5—
030060
036060
036090
2-1/2
3
3
313
321
321
Scroll
1
5.5
6.9
6.9
.057
.065
.065
1/17
2/17
2/17
12.7
9.1
9.1
2350
2350
2350
22
22
22
1/8 (825)
1/8 (825)
1/8 (825)
3/15
3/15
3/15
3.7
3.7
3.7
1000
1200
1200
10 x 10
10 x 10
10 x 10
1/4 (1075)
1/2 (1075)
1/2 (1075)
1000
1200
1200
10 x 10
11 x 10
11 x 10
1/2
3/4
3/4
2...38
2...38
3...38
2...46
2...46
3...46
610 ± 15
420 ± 25
20 ± 5
45 ± 10
042060
042090
3-1/2
3-1/2
382
382
9.0
9.0
.070
.070
2/17
2/17
12.3
12.3
2350
2350
22
22
1/8 (825)
1/8 (825)
3/15
3/15
4.7
4.7
1400
1400
11 x 10
11 x 10
3/4 (1075)
3/4 (1075)
1400
1400
11 x 10
11 x 10
3/4
3/4
2...38
3...38
2...46
3...46

Advertisement

Table of Contents
loading

Table of Contents

Save Article as PDF