Physical Data; Vapor Line Sizing/Cooling Capacity Loss; Vapor Line Sizing And Cooling Capacity Loss - Bryant Legacy 113ANC Series Product Data

Legacy line air conditioner for coastal applications with puron refrigerant
Table of Contents

Advertisement

UNIT SIZE SERIES
Operating Weight lb (kg)
Shipping Weight lb (kg)
Compressor Type
REFRIGERANT
Control
Charge lb (kg)
COND FAN
Air Discharge
Air Qty (CFM)
Motor HP
Motor RPM
COND COIL
Face Area (Sq ft)
Fins per In.
Rows
Circuits
VALVE CONNECT. (In. ID)
Vapor
Liquid
REFRIGERANT TUBES (In. OD)
Rated Vapor*
Vapor
Liquid
(0 ---50 ft / 0 --- 15.2 m) Tube Length)
Liquid (For Long --- Line applications)
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset
Note: See unit Installation Instruction for proper installation.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

LONG LINE APPLICATION: An application is considered
"Long line" when the total equivalent tubing length exceeds 80
ft. (24.38 m) or when there is more than 20 ft. (6.09 m) vertical
separation between indoor and outdoor units. These applications
require additional accessories and system modifications for
reliable system operation. The maximum allowable total
equivalent length is up to 250 ft. (76.2 m). The maximum
Maximum
Unit Nomi-
Vapor Line
Liquid Line
nal Size
Diameters
Diameters
(Btuh)
(In. OD)
(In. OD)
18000
1/2
1 Stage
3/8
5/8
Puron AC
5/8
24000
1 Stage
3/8
3/4
Puron AC
7/8
5/8
30000
1 Stage
3/8
3/4
Puron AC
7/8
5/8
36000
1 Stage
3/8
3/4
Puron AC
7/8
3/4
42000
1 Stage
3/8
7/8
Puron AC
1 1/8
3/4
48000
1 Stage
3/8
7/8
Puron AC
1 1/8
3/4
60000
1 Stage
3/8
7/8
Puron AC
1 1/8
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica-
tion Guidelines

PHYSICAL DATA

018---B
024---B
128
133
(58.1)
(60.3)
159
167
(72.1)
(75.7)
4.1
5.1
(1.9)
(2.3)
1881
2196
1/12
1/10
1100
1100
13.13
14.77
20
20
1
1
3
3
5/8
5/8
3/8
3/8
5/8
3/4
Standard
Application
26--- 50
51--- 80
81--- 100
(7.9--- 15.2)
(15.5--- 24.4)
(24.7--- 30.5)
1
2
3
0
0
1
0
1
1
0
0
0
0
0
0
1
2
3
0
0
1
0
0
0
1
2
4
0
1
1
0
0
0
0
1
2
0
0
1
0
0
0
0
1
2
0
0
1
0
0
0
1
2
4
0
1
2
0
0
0
030---B
036---B
155
167
(70.3)
(75.7)
193
205
(87.5)
(93.0)
Scroll
Puron (R--- 410A)
TXV (Puron Hard Shutoff)
5.8
6.8
(2.6)
(3.1)
Propeller Type, Direct Drive
Vertical
3167
3167
1/5
1/5
1100
1100
17.25
21.56
20
20
1
1
3
5
3/4
3/4
3/8
3/8
3/4
7/8
3/8"
3/8"
vertical separation is 200 ft. (60.96 m) when outdoor unit is
above indoor unit, and up to 80 ft. (24.38 m) when the outdoor
unit is below the indoor unit. Refer to Accessory Usage Guideline
below for required accessories. See Longline Application
Guideline for required piping and system modifications. Also,
refer to the table below for the vapor tube diameters based on the
total length to minimize the cooling capacity loss.
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
Long Line Application Requires Accessories
101--- 125
126--- 150
151--- 175
(30.8--- 38.1)
(38.4--- 45.7)
(46.0--- 53.3)
4
6
7
1
1
2
2
3
3
0
1
1
0
0
0
3
4
5
1
1
2
0
1
1
5
6
8
2
2
3
0
1
1
2
3
4
1
1
2
0
0
0
3
4
5
1
2
2
0
0
0
5
6
7
2
3
4
1
1
1
3
042---B
048---B
060---C
188
197
227
(85.3)
(89.4)
(103.0)
225
235
267
(102.1)
(106.6)
(121.1)
6.2
7.3
9.9
(2.8)
(3.3)
(4.5)
3810
3810
4046
1/5
1/5
1/4
800
800
800
17.60
20.12
17.60
20
20
20
1
1
2
4
5
8
7/8
7/8
7/8
3/8
3/8
3/8
7/8
1--- 1/8
1--- 1/8
1--- 1/8
176--- 200
201--- 225
226--- 250
(53.6--- 61.0)
(61.3--- 68.6)
(68.9--- 76.2)
8
9
10
2
3
3
4
4
5
1
1
1
0
0
0
6
7
8
2
2
3
1
1
1
9
10
12
3
4
4
1
2
2
4
5
6
2
2
3
0
0
0
5
6
7
2
3
3
0
1
1
9
10
11
4
5
5
1
1
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents