Siemens SITRANS DA400 Operating Instructions Manual page 78

Process monitoring
Table of Contents

Advertisement

Technical data
9.1 Device technical data
For connection to approved intrinsically safe electrical circuits with:
Alternative: Universal input 24 V digital signal
For connection to approved intrinsically safe electrical circuits with:
Alternative: Closing contact universal input
For connection to closing contact
Maximum values:
78
Maximum voltage U
i
Maximum short circuit current I
Maximum power P
i
Internal capacity C
i
Internal inductance L
i
Binary inputs
Input resistance
Signal level Low
Signal level High
Hysteresis
Maximum voltage U
o
Maximum short circuit current I
Maximum power P
o
Internal capacity C
i
Internal inductance L
i
Switching contacts, closing
Maximum voltage U
o
Maximum current I
o
Maximum power P
o
External inductance L
o
External capacity C
o
≤ 30 V
≤ 100 mA
i
≤ 1 W
≤ 11 nF
≤ 70 µH
Clamps 56 and 57
Clamps 66 and 67
Clamps 76 and 77
Clamps 86 and 87
> 19 kΩ
≤ 4.5 V or open
> 7 V
> 1 V
≤ 30 V
≤ 100 mA
o
≤ 1 W
≤ 11 nF
≤ 70 µH
Clamps 55 and 58
Clamps 65 and 68
Clamps 75 and 78
Clamps 85 and 88
≤ 10 V
≤ 1 mA
≤ 5 mW
100 mH
0.57 µF
SITRANS DA400 for material flow monitoring with protection against explosion
5.00 mH
1.00 mH
0.79 µF
1.08 µF
Operating Instructions, 09/2007, A5E00841152-01
0.20 mH
1.58 µF

Advertisement

Table of Contents
loading

Table of Contents