Warning - Siemens SITRANS F US Operating Instructions Manual

Ultrasonic flowmeter for use with sensor type sono 3100, sono 3300 and sonokit 1- and 2-tracks
Hide thumbs Also See for SITRANS F US:
Table of Contents

Advertisement

3.7

Warning

The pertinent regulations must be observed for electrical installation, in explosion risk areas in
particular:
• The rules and regulations governing the erection and operation of plants in explosion risks
areas (e.g.
• The EC Type Examination Certificate - Do not install the device under voltage. Danger of
electric shock! -The version for power supply
or PELV circuits.
The SITRANS FUS060 transmitter comply with the following electrical installation categories:
Version for 115 to 230 V AC: Installation Category II
Version for 24 V AC/DC: Installation Category II
General requirements:
• The power supply should be connected via a circuit breaker and fused via a fuse (max. 4 A).
• Use cables with a cross section of at least 1.5 mm
the power supply.
Lay
conduction of heat by the sensor/metering tube. Lay the cables so that they do not come into
contact with the hot sensor/metering tube.
• Lay signal cables separately from cables with voltages > 60 V.
• Use cables with twisted wire pairs.
• Full HART 5.1 specifications only with shielded cables.
• Earth transmitter housing.
Make the electrical connection as follows:
• Cables used for connection must have diameters fitting the glands.
• Use shielded cables for the outputs
• Compare data on rating plate with local power supply.
• Release lid lock of terminal box by turning the 3 mm hexagon socket screw.
• Unscrew lid from terminal box.
• Push power cable and signal cable through cable glands up to terminal block. Lay cables
in a bend in front of cable glands to prevent moisture getting into terminal block.
• Use signal cables with shielded wire pairs if analog output and pulse/frequency output are
to be used simultaneously and signals are transmitted in one cable.
For full performance at 10 KHz frequency on digital output 1, the capacitive load should not
exceed 100 nF (see also technical specification for digital output 1 on pages 6 and 7).
• Make the connection. Fit end ferrules to fine wire cables.
• Connect PE cable of power supply to earth terminal
so that the PE conductor is the last one to come away when the cables are pulled.
• Mount lid for power supply terminals in devices with ignition protection
ATEX II 2G Ex dem [ia/ib]
• Tighten cable gland and check strain relief.
• In devices with protection type
with certified blind plugs.
Screw lid tightly to housing, always use a tool. The sealing ring must be clean and
undamaged.
• Mount lid lock.
EN 60079-14).
heat-resistant cables if high temperatures can occur on the housing, eg due to
T6..T3.
SFIDK.PS.029.E5.02 / SW 2.01.07
DC
19 to 30 V may only be connected to SELV
2
and double or reinforced insulation for
ATEX II 2G Ex dem [ia/ib] T6..T3
in terminal box. Use a cable length
replace unused cable glands
15