Page 1
Quality control system on the development and production complies with requirements ISO 9001:2015 Dear customer, Company NOVATEK-ELECTRO LTD. thanks you for purchasing our products. You will be able to use properly the product after carefully studying the Operating Manual. Keep the Operating Manual throughout the service life of the product.
Page 2
During operation and maintenance the regulatory document requirements must be met, namely: – Regulations for Operation of Consumer Electrical Installations; – Safety Rules for Operation of Consumer Electrical Installations; – Occupational Safety when in Operation of Electrical Installations. RN-111M NOVATEK-ELECTRO...
Page 3
– it automatically turns ON the power load with the user adjusted time delay. If power load is less than 3.5 kW (16A) then RN-111M may operate with the power load directly using its own output terminals;...
Page 4
Maximal commutation current (active power load), A Tripping Voltage level accuracy, V to 3 Minimal operation voltage level at which RN-111M will keep working, V Maximal operation voltage level at which RN-111M will keep working, V Voltage hysteresis, V 4 - 5 Rower consumption (when de-energization load), W to 3.5...
Page 5
Operating Manual. 3.1.2 General instructions ATTENTION! RN-111M IS NOT DESIGNED FOR LOAD COMMUTATION IN CASE OF SHORT CIRCUITS. THEREFORE THEY SHOULD BE PROTECTED BY AUTOMATIC CIRCUIT BREAKERS (FUSES) WITH TRIPPING CURRENT NOT EXCEEDING 16 A.
Page 6
If power load is less than 3.5 kW (16 A) then it could be commutated directly by the output contacts of the RN-111M; if the power load is more than 16 A – then it should be commutated using contactor of appropriate rated parameters and the RN-111M should operate with the magnetic coil of the contactor.
Page 7
If the input voltage rises above Umax for more than one second, or when the input voltage rises by 30 V higher than Umax for more than 0.2 seconds, the RN-111M switches to the ALARM state and contacts 1, 2 (3) are open and contacts 2 ( 3), 4 are closed, the power load is disconnected.
Page 8
45 to +60 °C and relative humidity of no more than 80 %. 7. ACCEPTANCE CERTIFICATE Single phase voltage protection relay RN-111M was produced and accepted in accordance with the requirements of effective technical documentation and was recognized as suitable for operation.