Connect Pipes - CANVAC T-Series Installation Manual

Table of Contents

Advertisement

Available languages

Available languages

REFRIGERANT PIPING CONNECTION
STEP 4: CONNECT PIPES
When connecting refrigerant pipes, be careful not to use
excessive torque or to deform the piping in any way. Begin
by connecting the low-pressure pipe, then the high-pressure
pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum
bending radius is 10cm. See Fig.5.6.
INSTRUCTIONS FOR CONNECTING
PIPING TO INDOOR UNIT
1.
Align the center of the two pipes to be connected.
See Fig. 5.7.
2.
Tighten the flare nut as tightly as possible by hand.
3.
Using a spanner, grip the nut on the unit tubing.
4.
While firmly gripping the nut on the unit tubing, use a
torque wrench to tighten the flare nut according to the
torque values in the Torque Requirements table below.
Loosen the flaring nut slightly, then tighten again.
DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping.
Do not exceed torque requirements shown in the table above.
TORQUE REQUIREMENTS
Outer Diameter
of Pipe (mm)
Ø 6.35 (Ø 0.25")
Ø 9.52 (Ø 0.375")
Tightening Torque
Add. Tightening Torque
(N•cm)
1,500 (11lb•ft)
1,600 (11.8lb•ft)
2,500 (18.4lb•ft)
2,600 (19.18lb•ft)
59
Radius
Indoor unit tubing
(N•cm)
EN
≥10cm (4in)
fig 5.6
fig 5.7
Pipe
Flare nut
fig 5.8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qhw-ta09aQhw-ta12aQhw-ta41aQhx-ta09aQhx-ta12aQhx-ta41a

Table of Contents