INDOOR UNIT INSTALLATION
STEP 5: CONNECT DRAIN HOSE
By default, the drain hose is attached to the left-hand side
of the unit (when facing the back of the unit). However, it
can also be attached to the right-hand side.
1.
To ensure proper drainage, attach the drain hose on the
same side that your refrigerant piping exits the unit.
2.
Attach drain hose extension (purchased separately) to
the end of drain hose.
3.
Wrap the connection point firmly with Teflon tape to
ensure a good seal and to prevent leaks.
4.
Wrap the portion of the drain hose that will remain
indoors with foam pipe insulation to prevent condensa-
tion.
5.
Remove the air filter and pour a small amount of water
into the drain pan to make sure water flows from the
unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to Fig. 3.5.
DO NOT kink the drain hose.
DO NOT create a water trap.
DO NOT put the end of drain hose in
water or a container that will collect water.
PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks, the unused drain hole must
be plugged with the rubber plug provided.
fig 3.5
NOT CORRECT
Kinks in the drain hose
will create water traps.
NOT CORRECT
Kinks in the drain hose
will create water traps.
fig 3.7
NOT CORRECT
Do not place the end
of the drain hose in
water or in containers
that collect water. This
will prevent proper
drainage.
47
EN
CORRECT
Make sure there are no
kinks or dents in the drain
hose to ensure proper
drainage.
fig 3.6
fig 3.8