Canadian Two-Stage
B.7 Canadian Two-Stage
In this application, NAC1 from the Host FACP is providing the Canada 2-stage audible pattern to the FL-PS and NAC. NAC2 is provid-
ing Master Sync or a Steady Output, depending on its capabilities.
AC1
AC2
TB15
The following notes apply to Figure B.7.
FL-PS Output #1 is programmed to activate on Command Input #1 and slave mode (NAC follower).
FL-PS Output #2 is programmed depending on the host FACP capabilities.
– FACP NAC2 provides master sync: FL-PS Output #2 activate on Command Input 2, slave mode (NAC follower)
– FACP NAC2 provides steady output: FL-PS Output #2 activate Command Input 2, master mode (select appropriate strobe
manufacturer)
Additional FL-PS outputs can be mapped to command inputs and used to drive additional visual/audible or FL-PS units.
FL-PS Series Instruction Manual — P/N LS10227-001FL-E:B 3/29/2021
-
+
strobe circuit
-
+
-
+
-
+
Figure B.7 Canadian Two-Stage Wiring
-
+
horn circuit
-
+
-
+
-
+
NAC1
NAC2
Application Examples
Host FACP
43