Open/Short/Ground Fault Trip Values In Standby - Honeywell Fire-Lite FL-PS6 Instruction Manual

Table of Contents

Advertisement

Open/Short/Ground Fault Trip Values in Standby

FL-PS10(C): 120 VAC, 50/60 Hz, 6.2 amps maximum
Wire size: #12-14 AWG wire with 600V insulation
Command Input Circuits - TB5, TB6, TB7
Trigger Input Voltage: 9 - 32 VDC
Input Current Draw in Alarm Polarity: 9 - 32 volts, 14.0 mA maximum per input
Output Circuits - TB8-TB14
Supervised and power-limited
Voltage Rating: 24 VDC filtered
Current:
– FL-PS6: TB8-TB9 – 1A Regulated, 3A special applications; TB10-TB12 – 0.3A Regulated, 3A special applications
– FL-PS10: TB8-TB11 – 1.5A Regulated, 3A special applications; TB12-TB14 – 0.3A Regulated, 3A special applications
– Maximum total alarm current for all output:
FL-PS6 - 6.0 amps
FL-PS10 - 10.0 amps
Output Circuit Types:
– Class B NACs (require 2kΩ - 27kΩ End-of-Line Resistors) and/or Class A NACs using the optional ZNAC-PS Class A
converter module. Use Listed ELRs supplied by the FACP or compatible equipment manufacturer.
– Resettable or non-resettable outputs for 24 VDC power outputs or Class D door holder (max ripple voltage: 780mV
Refer to the Fire•Lite Device Compatibility Document #15384 for listed compatible devices.
For wiring requirements, refer to "Wire Requirements" on page 36.
Trouble, AC Loss, and Ground Fault (Canadian models only) Relay Contact Rating - TB1-TB3
Fail-safe Form-C relay (normally energized, transfers with loss of power) for AC Loss and Trouble
4.0 amps @ 30 VDC resistive
Secondary Power (battery) Charging Circuit - TB15
Supervised, non-power-limited
Supports lead acid type batteries only
Float Charge Voltage: 27.6 VDC
Maximum Peak Charge Current: 2.47A
Maximum Nominal Charge Current: 1.5 A
Maximum Battery Capacity: 33.0 AH (with onboard battery charger)
Minimum Battery Capacity: 7.0 AH
NOTE: The FL-PS only supports 7AH or 18AH batteries in the cabinet. Other battery capacities up to 33AH will not fit in the cabinet due to
physical dimensions and require a separate battery cabinet.
1.4 Open/Short/Ground Fault Trip Values in Standby
Table 1.1 lists the earth fault resistance detection in standby for each applicable terminal on the FACP.
Value of the resistance in between any circuit terminal to Earth, which will cause the Ground Fault detection, depends on the ELR cho-
sen for inputs and output circuits. This resistance will vary from 9.9K down to 0 Ohm.
Table 1.2 lists the open/short trip values and restoral values in standby for the NAC circuits on the FACP.
FL-PS Series Instruction Manual — P/N LS10227-001FL-E:B 3/29/2021
Output Circuit
NAC 1-5/7
NAC 1-5/7
ZNAC-PS 1-5/7
ZNAC-PS 1-5/7
Table 1.1 Earth Fault Trip Values
Circuit
Fault
NAC 1-5/7
Short
NAC 1-5/7
Open
ZNAC-PS 1-5/7
Short
ZNAC-PS 1-5/7
Open
Table 1.2 NAC Open/Short Trip Values
Terminal
Trip Resistance (in ohms)
+
9.9K or lower
-
9.2K or lower
+
9.9K or lower
-
9K or lower
Trip Resistance (in ohms)
1.6K or lower
55K or higher
1.6K or lower
45K or higher
System Overview
RMS
Restore Value
1.7K or higher
33K or lower
1.7K or higher
21K or lower
)
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite fl-ps6cFire-lite fl-ps10Fire-lite fl-ps10c

Table of Contents