LED Indicators
Output Circuit Status LEDs (red)
Output inactive
Output active
Output Circuit Trouble LEDs (yellow)
No Fault
Fault Condition (Normal/Standby Mode):
Wire Supervision
Class A or B Open circuit
1 short blink (250ms)
Fault Condition (Normal/Standby Mode):
Wire Supervision
Class A or B Short Circuit
2 short blinks (250ms)
Fault Condition:
Aux Power Supervision
Class A Open circuit
(ZNAC-PS Circuit #1 and #2 only)
3 short blinks (250ms)
Fault Condition:
Power limit condition (individual ckt overload)
4 short blinks per individual circuit (250ms)
Fault Condition:
Power limit condition (panel overload)
4 short blinks on all output circuits (250ms)
Operating Mode Fault:
Power Supply not in Normal Operating mode
1 short blink from right to left across all output
circuits.
Set positions 9 and 10 on S1 to the ON
position.
30
LED is OFF
LED is ON constant
LED is OFF
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
FL-PS Series Instruction Manual — P/N LS10227-001FL-E:B 3/29/2021
pause
1000ms
pause
1000ms
pause
1000ms
pause
1000ms
pause
1000ms