NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as
indicated below:
Program feature or
UL864/2572 and
option
ULC S527? (Y/N)
Door Holder Dropout
Delay
AC Loss Delay Timer
1
A two hour delay is only permitted on an addressable FACP.
This section describes the programming options available via DIP switch settings. The FL-PS can be field programmed using DIP
switches S1-S8 which are located at the bottom of the circuit board. S1 controls the global options of the power supply and S2-S8 control
the functions of each output circuit, respectively. Refer to the following illustration for switch locations and DIP switch placement in the
ON and OFF positions.
Important: Activate output DIP switch changes by setting S1 positions 9 and 10 appropriately. Refer to Table 3.6 on page 24 for DIP
Switch programming settings.
TB15
S1
ON
1 2 3 4 5 6 7 8 9 10
Switches 1 through 9 shown
in OFF (Open) position
22

Section 3: Programming Options

Permitted in
Y
Refer to "AC Loss Door Holder Dropout Timer" on
page 24.
• Does not drop
• 15 seconds
• 5 minutes
• 60 seconds
Y
Refer to "AC Fail Indication Delay" on page 24.
• 30 hours
• 12 hours
• 2 hours
• none
Table 3.1 Agency-Permitted Programming Settings
Switch 10 shown in
ON (Closed) position
Figure 3.1 Field Programming DIP Switches
PARTIES
Possible settings
S2-S8
ON
1 2 3 4 5 6 7 8
Switches 1 through 7 shown
in OFF (Open) position
FL-PS Series Instruction Manual — P/N LS10227-001FL-E:B 3/29/2021
Settings
Settings
permitted in
permitted in
UL 864 / UL2572
ULC S527
• Does not drop
• Does not drop
• 15 seconds
• 15 seconds
• 60 seconds
• 60 seconds
• 5 minutes
• 5 minutes
1
• 2 hours
• 2 hours
• none
• none
Switch 8 shown in
ON (Closed) position