The FL-PS power supply has 3 system LED indicators for Power, Batt/Chgr Fault, and Ground Fault. In addition, each available output
circuit also has 2 status LEDs. Refer to Figure 1.1 on page 10 for LED locations. A description of each FL-PS LED indication is given
below.
Ground Fault LED (yellow)
No Fault
Fault Condition:
ground fault
Power LED (green)
No Fault
Fault Condition:
AC power loss (or brownout)
1 short blink (250ms)
Battery fault LED (yellow)
No Fault
Fault Condition:
Charging path (FETs) failure
1 short blink (250ms)
Fault Condition:
Charger voltage too low or
Charger Diode Fault
2 short blinks (250ms)
Fault Condition:
Battery discharged/overcharged
3 short blinks (250ms)
Fault Condition:
Battery disconnected/fully
discharged
4 short blinks (250ms)
FL-PS Series Instruction Manual — P/N LS10227-001FL-E:B 3/29/2021

Section 4: LED Indicators

LED is OFF
LED is ON constant
LED is ON constant
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
LED is OFF
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
pause
1000ms
pause
1000ms
pause
1000ms
pause
1000ms
pause
1000ms
29