S8600, S8610 Troubleshooting Guide - Honeywell S8600 Manual

Intermittent pilot modules
Table of Contents

Advertisement

• Make sure electrical connections are clean and tight.
Replace damaged wire with moisture-resistant No.
18 wire rated for continuous duty up to 105 C [221
F].
• Check for cracked ceramic insulator, which can cause
short to ground, and replace igniter-sensor if neces-
sary.
• At the gas control, disconnect main valve wire from
the TH or MV terminal.
• Turn on power and set thermostat to call for heat. The
pilot should light but the main burner will remain off
because the main valve actuator is disconnected.
• Check the pilot flame. Make sure it is blue, steady and
envelops 3/8 to 1/2 in. [10 to 13 mm] of the flame rod.
See Fig. 13 for possible flame problems and their
causes.
• If necessary, adjust pilot flame by turning the pilot
START
TURN GAS SUPPLY OFF.
TURN THERMOSTAT
(CONTROLLER) TO CALL
NO
FOR HEAT
POWER TO MODULE?
(24V NOMINAL)
YES
NO
SPARK ACROSS
IGNITER/SENSOR GAP?
(S8660, S8670, S8680
HAVE 45 SECOND [NOMINAL]
PREPURGE BEFORE SPARK
STARTS.)
YES
TURN GAS SUPPLY ON
NO
AND RECYCLE CALL
FOR HEAT
PILOT BURNER LIGHTS?
YES
SPARK STOPS WHEN
NO
PILOT IS LIT?
YES
MAIN BURNER LIGHTS?
NO
YES
SYSTEM RUNS UNTIL
NO
CALL FOR HEAT ENDS?
YES
CALL FOR HEAT ENDS
NO
SYSTEM SHUTS OFF?
YES
TROUBLESHOOTING
ENDS
Before troubleshooting, familiarize yourself with the startup and checkout procedure.
NOTE: Models with TH-W terminal (7) must have call for heat 24 Vac supply connected to the TH-W terminal.
Models with no TH-W terminal must have call for heat 24 Vac supply connected to 24V terminal (6).
Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring. Also,
check air proving switch on combustion air blower system (if used) and that vent damper (if used) is open and
end switch is made.
Pull ignition lead and
check spark at module.
Spark okay?
YES
Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and
boot from excessive temperatures.
Check that all manual gas valves are open, supply tubing and pressures are good, and pilot burner orifice
is not blocked.
Check electrical connections between module and pilot operator on gas control.
Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not,
replace module.
NOTE: It may be necessary to recycle the call for heat to clear the pilot supply tubes of air.
NOTE: If S86XXB,H,D,J goes into lockout, reset system. For S86XXC,M,U,J,K, wait 6 min.
nom. for retry or reset system.
Check continuity of ignition cable and ground wire.
Clean flame rod.
Check electrical connections between flame rod and module.
Check for cracked ceramic flame rod insulator.
Check that pilot flame covers flame rod and is steady and blue.
Adjust pilot flame.
If problem persists, replace module.
Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.
Check electrical connections between module and gas control. If okay, replace gas control or gas control
operator.
NOTE: If S86XXB,H,D,J goes into lockout, reset system. For S86XXC,M,U,J,K, wait 6 min.
nom. for retry or reset system.
Check continuity of ignition cable and ground wire.
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at
the time of checkout.
Check that pilot flame covers flame rod and is steady and blue.
If checks are okay, replace module.
Check for proper thermostat (controller) operation.
Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas
control.
Repeat procedure until troublefree operation is obtained.
Fig. 14—S8600, S8610 troubleshooting guide.
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
Website:
https://www.add-furnace.com/
Line ID: @add11 e-mail: add028883472@gmail.com
adjustment
clockwise
counterclockwise
lowing adjustment, always replace pilot adjustment
cover screw and tighten firmly to assure proper gas
control operation.
• Set thermostat below room temperature to end call
for heat.
Recheck ignition sequence as follows.
• Reconnect main valve wire.
• Set thermostat to call for heat.
• Watch ignition sequence at burner.
• If spark still doesn't stop after pilot lights, replace
ignition module.
• If main burner doesn't light or if main burner lights but
system locks out, check module, ground wire and gas
control as described in appropriate troubleshooting
chart, Fig. 14 or 15.
On models with vent damper plug, make sure vent damper
NO
has not been installed, then removed. Replace vent damper
if necessary.
On other models, replace module.