Buffer module 24 v dc, 40 a, 160 ms

Advertisement

Quick Links

Documentation | EN
PS2001-2440-0000
Buffer Module 24 V DC, 40 A, 160 ms
2021-06-21 | Version: 1.0

Advertisement

Table of Contents
loading

Summary of Contents for Beckhoff PS2001-2440-0000

  • Page 1 Documentation | EN PS2001-2440-0000 Buffer Module 24 V DC, 40 A, 160 ms 2021-06-21 | Version: 1.0...
  • Page 3: Table Of Contents

    4.17 Environment ............................ 22 4.18 Protective functions and safety features.................. 23 4.19 Dielectric strength .......................... 23 4.20 Declaration of conformity and approvals .................. 24 4.21 Dimensions and weight ........................ 25 5 Appendix .............................. 26 Accessories ............................. 26 Documentation issue status ...................... 27 Support and Service ........................ 28 PS2001-2440-0000 Version: 1.0...
  • Page 4 Table of contents Version: 1.0 PS2001-2440-0000...
  • Page 5: Overview

    Dimensions (W x H x D) 64 x 124 x 142 mm Weight 1040 g Markings/approvals CE, cULus *) All values typical for 24 V, 40 A, +25 °C ambient temperature and after a warm-up time of five minutes, unless specified otherwise PS2001-2440-0000 Version: 1.0...
  • Page 6: Foreword

    , XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners. Patent Pending...
  • Page 7: Safety Instructions

    All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
  • Page 8 2 cm below the device. • The device is designed for operation in the relative humidity range between 5 % and 95 %. • For EMC reasons the signal cables (ready, active, inactive) must be shorter than 30 m. Version: 1.0 PS2001-2440-0000...
  • Page 9: Terminology And Abbreviations

    A value followed by the unit Vac or Vdc is an instantaneous value that does not contain any additional tolerances. A keyword indicating a choice without implied preference. shall A keyword indicating a mandatory requirement. should A keyword indicating a choice with a clearly preferred method of implementation. PS2001-2440-0000 Version: 1.0...
  • Page 10: Basics

    The buffer module requires no control wiring. It can be inserted anywhere in parallel with the load circuit. Buffer modules can be connected in parallel in order to increase the output current capacity or the hold-up time. Fig. 4: Parallel connection without control wiring Version: 1.0 PS2001-2440-0000...
  • Page 11 Basics Fig. 5: Typical wiring Fig. 6: Transition behavior PS2001-2440-0000 Version: 1.0...
  • Page 12: Technical Data, Application Notes, Wiring

    Within the input voltage range the device can either be in power supply mode or buffer mode. Normal operating voltage range: The normal operating voltage range describes the supply voltage that supports the full functionality of the buffer module (including charging) without entering buffer mode. Fig. 7: Selection of a suitable power supply Version: 1.0 PS2001-2440-0000...
  • Page 13 Technical data, application notes, wiring Fig. 8: Output characteristic curve in buffer mode, 22.5 V fixed mode, typ. PS2001-2440-0000 Version: 1.0...
  • Page 14: Selection Of The Backup Threshold Voltage

    This setting is recommended for all applications in which 22.5 V is too low for the application or if the buffer module is placed near the power supply. The factory setting is fixed mode; if the jumper is missing, this also means fixed mode. Version: 1.0 PS2001-2440-0000...
  • Page 15: Buffer Storage Time

    Min. 160 ms At 22.5 V, 40 A Min. 320 ms At 22.5 V, 20 A Typ. 250 ms At 22.5 V, 40 A Typ. 500 ms At 22.5 V, 20 A Typ. 62 s At 22.5 V, 0.1 A Fig. 9: Buffer time, typ. Fig. 10: Buffer time for low buffer currents, typ. PS2001-2440-0000 Version: 1.0...
  • Page 16: Charging Time

    Recharging 40 s Recharging Initial charging is the first charging after applying the voltage to the buffer module. Recharging is the charging of the internal capacitors after voltage interruptions lasting less than 2 minutes. Fig. 11: Charging time, recharging Version: 1.0 PS2001-2440-0000...
  • Page 17: Operating Diagrams

    Technical data, application notes, wiring Operating diagrams Fig. 12: Operating diagram Fig. 13: Signal circuit diagram PS2001-2440-0000 Version: 1.0...
  • Page 18: Active" Signal

    9 is higher than 10 V. The buffering functions again below 6 V. Insulation voltage See chapter Dielectric strength [} 23] Efficiency and losses Efficiency Typ. >99% Power supply mode, 40 A output current, capacitors fully charged Power losses Typ. 1.9W Power supply mode, 0 A output current, capacitors fully charged Version: 1.0 PS2001-2440-0000...
  • Page 19: Lifetime Expectancy

    272,000h Standby mode, 40 °C, Ground Benign GB40 217F 433,000h Standby mode, 25 °C, Ground Benign GB25 95,000h Standby mode, 40 °C, Ground Fixed GF40 143,000h Standby mode, 25 °C Ground Fixed GF25 4.12 Functional wiring diagram Fig. 14: Functional wiring diagram PS2001-2440-0000 Version: 1.0...
  • Page 20: Terminals And Wiring

    = solid wire f* = stranded wire a* = with ferrule 4.14 Connection diagrams Fig. 15: General connection diagrams; signals that are supplied by an external voltage source Fig. 16: Parallel connection of buffer modules; decoupling of buffered lines Version: 1.0 PS2001-2440-0000...
  • Page 21: Front Side And Operating Elements

    - Option 2: Variable mode (jumper in position 1-2): the device switches to buffer mode when the input voltage drops by 1 V. Voltage changes slower than 0.54 V/s are ignored if the voltage is above 22.5 V. Buffering begins immediately below 22.5 V. For further details, refer also to the chapter Selection of the backup threshold voltage [} 14] PS2001-2440-0000 Version: 1.0...
  • Page 22: Emc

    IEC 62103, EN 62477-1, above an altitude of 2000 m Degree of pollution IEC 62103, EN 62477-1, not conductive LABS compatibility The device does not release any silicone or other LABS-critical substances and is suitable for use in painting plants. Version: 1.0 PS2001-2440-0000...
  • Page 23: Protective Functions And Safety Features

    Fig. 18: Dielectric strength Type test 500 Vac 500 Vac 500 Vac Component test 500 Vac 500 Vac 500 Vac Field test 500 Vac 500 Vac 500 Vac Settings for the field test cut-off > 1 mA > 1 mA > 1 mA current PS2001-2440-0000 Version: 1.0...
  • Page 24: Declaration Of Conformity And Approvals

    Applicable for US and Canada UK Declaration of Conformity: Trade conformity assessment for England, Scotland and Wales The UKCA mark indicates conformity with the UK Statutory Instruments 2016 No. 1101 (LVD) 2016 No. 1091 (EMC) and 2012 No. 3032 (RoHS) Version: 1.0 PS2001-2440-0000...
  • Page 25: Dimensions And Weight

    Housing: Aluminum alloy Cover: galvanized steel Ingress protection Small parts such as screws, nuts, etc. with a diameter greater than 3.5 mm Installation clearances See chapter on Safety instructions and installation requirements [} 8] Fig. 19: PS9011-2440-0000 – front/side view PS2001-2440-0000 Version: 1.0...
  • Page 26: Appendix

    For lateral DIN rail mounting, the previously removed aluminum brackets and the black plastic slider must be mounted on the steel bracket. Fig. 21: Isometric view, lateral mounting without and with DIN rail bracket; mounting dimensions Version: 1.0 PS2001-2440-0000...
  • Page 27: Documentation Issue Status

    Appendix Documentation issue status Version Comment - Addenda & corrections public issue - Addenda & corrections - Preliminary documentation for PS9011-2440-0000 PS2001-2440-0000 Version: 1.0...
  • Page 28: Support And Service

    Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: https://www.beckhoff.com You will also find further documentation for Beckhoff components there.
  • Page 30 More Information: www.beckhoff.com/ps9011-2440-0000 Beckhoff Automation GmbH & Co. KG Hülshorstweg 20 33415 Verl Germany Phone: +49 5246 9630 info@beckhoff.com www.beckhoff.com...