Dimensions (W x H x D) 64 x 124 x 142 mm Weight 1040 g Markings/approvals CE, cULus *) All values typical for 24 V, 40 A, +25 °C ambient temperature and after a warm-up time of five minutes, unless specified otherwise PS2001-2440-0000 Version: 1.0...
, XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners. Patent Pending...
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Page 8
2 cm below the device. • The device is designed for operation in the relative humidity range between 5 % and 95 %. • For EMC reasons the signal cables (ready, active, inactive) must be shorter than 30 m. Version: 1.0 PS2001-2440-0000...
A value followed by the unit Vac or Vdc is an instantaneous value that does not contain any additional tolerances. A keyword indicating a choice without implied preference. shall A keyword indicating a mandatory requirement. should A keyword indicating a choice with a clearly preferred method of implementation. PS2001-2440-0000 Version: 1.0...
The buffer module requires no control wiring. It can be inserted anywhere in parallel with the load circuit. Buffer modules can be connected in parallel in order to increase the output current capacity or the hold-up time. Fig. 4: Parallel connection without control wiring Version: 1.0 PS2001-2440-0000...
Within the input voltage range the device can either be in power supply mode or buffer mode. Normal operating voltage range: The normal operating voltage range describes the supply voltage that supports the full functionality of the buffer module (including charging) without entering buffer mode. Fig. 7: Selection of a suitable power supply Version: 1.0 PS2001-2440-0000...
This setting is recommended for all applications in which 22.5 V is too low for the application or if the buffer module is placed near the power supply. The factory setting is fixed mode; if the jumper is missing, this also means fixed mode. Version: 1.0 PS2001-2440-0000...
Min. 160 ms At 22.5 V, 40 A Min. 320 ms At 22.5 V, 20 A Typ. 250 ms At 22.5 V, 40 A Typ. 500 ms At 22.5 V, 20 A Typ. 62 s At 22.5 V, 0.1 A Fig. 9: Buffer time, typ. Fig. 10: Buffer time for low buffer currents, typ. PS2001-2440-0000 Version: 1.0...
Recharging 40 s Recharging Initial charging is the first charging after applying the voltage to the buffer module. Recharging is the charging of the internal capacitors after voltage interruptions lasting less than 2 minutes. Fig. 11: Charging time, recharging Version: 1.0 PS2001-2440-0000...
9 is higher than 10 V. The buffering functions again below 6 V. Insulation voltage See chapter Dielectric strength [} 23] Efficiency and losses Efficiency Typ. >99% Power supply mode, 40 A output current, capacitors fully charged Power losses Typ. 1.9W Power supply mode, 0 A output current, capacitors fully charged Version: 1.0 PS2001-2440-0000...
= solid wire f* = stranded wire a* = with ferrule 4.14 Connection diagrams Fig. 15: General connection diagrams; signals that are supplied by an external voltage source Fig. 16: Parallel connection of buffer modules; decoupling of buffered lines Version: 1.0 PS2001-2440-0000...
- Option 2: Variable mode (jumper in position 1-2): the device switches to buffer mode when the input voltage drops by 1 V. Voltage changes slower than 0.54 V/s are ignored if the voltage is above 22.5 V. Buffering begins immediately below 22.5 V. For further details, refer also to the chapter Selection of the backup threshold voltage [} 14] PS2001-2440-0000 Version: 1.0...
IEC 62103, EN 62477-1, above an altitude of 2000 m Degree of pollution IEC 62103, EN 62477-1, not conductive LABS compatibility The device does not release any silicone or other LABS-critical substances and is suitable for use in painting plants. Version: 1.0 PS2001-2440-0000...
Fig. 18: Dielectric strength Type test 500 Vac 500 Vac 500 Vac Component test 500 Vac 500 Vac 500 Vac Field test 500 Vac 500 Vac 500 Vac Settings for the field test cut-off > 1 mA > 1 mA > 1 mA current PS2001-2440-0000 Version: 1.0...
Applicable for US and Canada UK Declaration of Conformity: Trade conformity assessment for England, Scotland and Wales The UKCA mark indicates conformity with the UK Statutory Instruments 2016 No. 1101 (LVD) 2016 No. 1091 (EMC) and 2012 No. 3032 (RoHS) Version: 1.0 PS2001-2440-0000...
Housing: Aluminum alloy Cover: galvanized steel Ingress protection Small parts such as screws, nuts, etc. with a diameter greater than 3.5 mm Installation clearances See chapter on Safety instructions and installation requirements [} 8] Fig. 19: PS9011-2440-0000 – front/side view PS2001-2440-0000 Version: 1.0...
For lateral DIN rail mounting, the previously removed aluminum brackets and the black plastic slider must be mounted on the steel bracket. Fig. 21: Isometric view, lateral mounting without and with DIN rail bracket; mounting dimensions Version: 1.0 PS2001-2440-0000...
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: https://www.beckhoff.com You will also find further documentation for Beckhoff components there.