Parallel use to increase power ...................... 29 Series connection .......................... 29 Inductive and capacitive loads...................... 30 Charging batteries ........................... 30 Operation on two phases......................... 30 Use in a tightly sealed enclosure ..................... 30 5 Appendix .............................. 32 Documentation issue status ...................... 32 Support and Service ........................ 33 PS1021-2405-0000 Version: 1.0...
Page 4
Table of contents Version: 1.0 PS1021-2405-0000...
• Full power between -10°C and +55°C • Including DC-OK relay contact The PS1021-2405-0000 is a 1-phase 24 V power supply with an output current of 5 A and an output power of 120 W. On the input side, the device has a wide-range input and an input inrush current limitation.
, XFC , XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Page 8
Foreword Safety instructions and installation requirements for the PS1021-2405-0000 power supply DANGER Danger of electric shock, fire, injuries, injuries resulting in death! • Do not use the power supply without proper grounding (protective conductor). Use the terminal at the in- put terminal strip for the earth connection, not one of the screws on the housing.
50 Hz. AC 120 V parameters are valid for a mains frequency of 60 Hz. A keyword indicating a choice without implied preference. shall A keyword indicating a mandatory requirement. should A keyword indicating a choice with a clearly preferred method of implementation. PS1021-2405-0000 Version: 1.0...
*) The power factor is the ratio of real (or active) power to apparent power in an AC circuit. **) The peak factor is the mathematical ratio of the peak value to the RMS value of the input current waveform. Fig. 1: Input voltage range; switch-on behavior definitions Version: 1.0 PS1021-2405-0000...
Page 11
Technical data, mounting, wiring Fig. 2: Input current over output current; power factor over output current PS1021-2405-0000 Version: 1.0...
At 24V, 2.5A, see Fig. Hold- up time over input voltage Typ. 26ms 51ms 50ms At 24V, 5A, see Fig. Hold- up time over input voltage Min. 22ms 43ms 42ms At 24V, 5A, see Fig. Hold- up time over input voltage Version: 1.0 PS1021-2405-0000...
Page 15
Technical data, mounting, wiring Fig. 5: Hold-up time over input voltage; switch-off behavior, definitions PS1021-2405-0000 Version: 1.0...
Contact load capacity Maximum 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, ohmic load Minimum permissible load: 1mA at 5Vdc Insulation voltage See the dielectric strength table in the chapter on Dielectric strength Fig. 6: Behavior of the DC-OK relay contact Version: 1.0 PS1021-2405-0000...
75% of the nominal load during 25% of the time and 100% of the nominal load during the remaining time. Fig. 7: Efficiency over output current; losses over output current Fig. 8: Efficiency over input voltage; losses over input voltage PS1021-2405-0000 Version: 1.0...
645,000 h At 24V, 5A and 40°C; Ground Benign GB40 217F 872,000 h 842,000 h 839,000 h At 24V, 5A and 25°C; Ground Benign GB25 165,000 h 164,000 h 168,000 h At 24V, 5A and 40°C; Ground Fixed GF40 206,000 h 205,000 h 211,000 h At 24V, 5A and 25°C; Ground Fixed GF25 Version: 1.0 PS1021-2405-0000...
• Observe the national installation rules and regulations! • Do not use the device without PE connection. • Make sure that all single wires of a strand are connected to the terminal! • Unused terminals should be tightened firmly. • Ferrules are permitted. Version: 1.0 PS1021-2405-0000...
Technical data, mounting, wiring 3.11 Front side and operating elements Fig. 10: PS1021-2405-0000, front Input terminals (screw terminals) Designation (A) Description Mains input N Mains input L Protective conductor, PE Output terminals (screw terminals) Designation (B) Description two identical positive poles, positive output...
Tested in conjunction with DIN rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard mounting position. For AC 208V mains, AC 200-220V values must be used. Fig. 11: Output current over ambient temperature; output current over installation altitude PS1021-2405-0000 Version: 1.0...
(column D). We recommend connecting the DC-OK pins and the output pins when performing the test. Type test 2500Vac 3000Vac 1000Vac 500Vac Component test 5s 2500Vac 2500Vac 500Vac 500Vac Field test 2000Vac 2000Vac 500Vac 500Vac Setting the cut-off current > 10mA > 10mA > 15mA > 1 mA PS1021-2405-0000 Version: 1.0...
Technical data, mounting, wiring 3.16 Declaration of conformity and approvals EU declaration of conformity UL Certificate: UL 61010-1/2-201, Applicable for US and Canada Version: 1.0 PS1021-2405-0000...
370g Plastic material of the Flame retardant polycarbonate (PC) - UL94-V0 housing Vicat softening temperature specified at 149°C according to ASTM D1525 Installation clearances See chapter on Safety instructions and installation requirements [} 8] Fig. 13: PS1021-2405-0000 front/side view PS1021-2405-0000 Version: 1.0...
The following two examples show typical voltage drops for ohmic loads: Fig. 14: 10A peak current (ohmic load) for 50ms, the output voltage drops from 24V to 17V Fig. 15: 25A peak load (ohmic load) for 5ms, the output voltage drops from 24V to 9V. Version: 1.0 PS1021-2405-0000...
Restrictions: Keep a mounting distance of 15mm (left/right) between two power supplies and do not install the power supplies above each other. Remember that leakage current, electromagnetic interference, input inrush current and harmonics increase when using multiple power supplies. PS1021-2405-0000 Version: 1.0...
When the power supply is installed in a tightly sealed enclosure, the temperature inside the housing is higher than outside. In this case, the temperature inside the housing is considered the ambient temperature for the power supply. Version: 1.0 PS1021-2405-0000...
Page 31
IP66 PK 9516 100, plastic PK 9516 100, plastic Input voltage 230Vac 230Vac Load 24V, 4A; (=80%) 24V, 5A; (=100%) Temperature inside 38.9°C 41.5°C the housing Temperature outside 24.2°C 24.4°C the housing Temperature 14.5K 17.1K increase PS1021-2405-0000 Version: 1.0...
Appendix Appendix Documentation issue status Version Comment - First public issue - Corrections and addenda - Provisional documentation for PS1021-2405-0000 Version: 1.0 PS1021-2405-0000...
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: https://www.beckhoff.com/english/beckhoff/world.htm You will also find further documentation for Beckhoff components there.