Electrical Installation - ABB MicroFlex e190 Quick Installation Manual

Hide thumbs Also See for MicroFlex e190:
Table of Contents

Advertisement

6

Electrical installation

Notes:
(1) If shielded supply (input) cable is used, and
the conductivity of the shield is less than 50%
of the conductivity of a phase conductor, use a
cable with a ground conductor or a separate PE
cable.
(2) For motor cabling, use a separate ground
cable if the conductivity of the motor cable
shield is less than 50% of that of a phase
conductor and the cable has no symmetrical
ground conductors.
(3) MicroFlex e190 can be powered from a DC
supply. See user's manual.
(4) AC supply,1-phase 200...240 V or 3-phase
200...240 V phase-to-phase (±10%).
Quick installation guide - MicroFlex e190
Power cabling: input
• Attach the included terminal blocks to the
drive.
• Connect the supply, resistor (if present) and
motor cables to the appropriate terminals of
the drive.
• Strip the power cables so that the shields are
bare at the cable clamps.
0.5...0.6 N·m
(4.4...5.3 lbf·in)